
Federal Pacific K-Factor Transformers
To Order Federal Pacific
Transformers We Recommend TEMCo
Ph:
1-800-613-2290
Or 1-510-490-2187
Link:
Power Transformer |
Application
With today’s modern electronic, electrical components and circuitry
constantly changing, the demand is forced upon the electrical power
industry to produce and supply a clean source of electrical energy.
The Problem
The extensive utilization of solid state power conversion technologies
has created new problems for the power industry and power engineer
designer. This technology, called Switch Mode Power Systems (SMPS),
consists of various types of solid state switching elements. These
switching elements are solid state devices such as: SCR’s, DIAC’s,
transistors and capacitors. These switching devices are in computers,
copy machines, fax machines, tele-communications equipment, solid-state
drives, and controls, energy-efficient lighting ballasts, and numerous
types of DC-Power Loads. These solid state elements continuously switch
on and off producing non-linear or non-sinusoidal wave shapes in the
current supplied from the energy source.
While a linear load uses current from the AC source continuously over
the sinusoidal cycle, a non-linear load (such as the SMPS) uses current
in large pulses from the AC source, which creates harmonic distortion.
These non-linear current pulses may exceed the nameplate ampere rating
of the power source and may cause transformers to run hotter than
expected, even when these transformers are supplying less than 50% of
their rated nameplate capacity.
With non-linear loads, overloaded neutrals are also showing up in
three-phase panel boards serving single-phase loads. In some cases the
neutral conductor carries 180 Hertz currents, rather than 60 Hertz
currents. This phenomenon is called triplen harmonics. Triplens are
multiples of three, which do not cancel but are additive in the neutral
conductor.
What Are Harmonics
As defined by ANSI/IEEE Std. 519-1981
Harmonic components are represented by a periodic wave having a
frequency that is an integral multiple of the fundamental frequency. In
other words, harmonics are voltages of currents at frequencies that are
integer multiples of the fundamental (60Hz) frequency , e.g. 120 Hz, 180
Hz, 240 Hz, 300 Hz, etc. Harmonics are designed by their harmonic
number, or multiple of the fundamental frequency. Thus, a harmonic with
a frequency of 180 Hz (three times the 60 HX fundamental Frequency) is
called the 3rd harmonic.
Harmonics superimpose themselves on the fundamental waveform, distorting
it and changing its magnitude. For instance, when a sine wave voltage
source is applied to a non-linear load connected from phase-to-neutral
on a 3-phase, 4-wire wye circuit, the load itself will draw a current
wave made up of the 60-Hz fundamental frequency of the voltage source
plus 3rd and higher order odd harmonic (multiples of the 60 Hz
fundamental frequency), which are all generated by the non-linear load.
It is not uncommon for portions of an industrial power system to have 15
to 25% of Total Harmonic Distortion (THD). THD is calculated as the
square root of the sum of the squares of all harmonics, divided by
the normal 60 hertz value. This yields a root-mean-square (RMS) value of
distortion as a percentage of the fundamental 60 hertz waveform.
Therefore, THD is the percent of odd harmonics (3rd, 5th, 7th, …,
25th,…) present in the load which can affect the transformer. This
condition is called a “Non-Linear Load” or “Non-Sinusoidal Load”.
For dry type transformers, to determine what amount of harmonic content
is present, a “K” factor calculation is made instead of using the THD
formula. The total amount of harmonics will determine the percentage of
non-linear load, which can be specified with the following examples:
(A) 50% Non-Linear Load (K-4 Rating)
16.7% of the rated current at the 3rd Harmonic
10% of the rated current at the 5th Harmonic
7.1% of the rated current at the 7th Harmonic
5.6% of the rated current at the 9th Harmonic
Beyond the 9th Harmonic the percentages of the fundamental current
through the percentages of the fundamental current through the 25th
Harmonic shall be equal to the reciprocal of the odd harmonic number
involved times 0.5.
The FPType FHK-4 series transformer is designed for 100% linear load
plus 50% non-linear load which can operated at a total 1 (pu) h K-factor
load value of 4.0.
(B) 100% Non-Linear Load (K-13 Rating)
33.3% of the rated current at the 3rd harmonic
20.0% of the rated current at the 5th harmonic
14.3% of the rated current at the 7th harmonic
11.1% of the rated current at the 9th harmonic
Beyond the 9th Harmonic the percentages of the fundamental current
through the 25th Harmonic shall be equal to the reciprocal of the odd
harmonic number involved times 1.0.
The FPType FHK 13 series transformer is designed for 100% linear load
plus 100% non-linear load which can operate at a total (1 (pu) h)
K-factor load value of 13.0
(C) 125% Non-Linear Load (K-20 Rating)
41.7% of the rated current at the 3rd harmonic
25.0% of the rated current at the 5th harmonic.
17.9% of the rated current at the 7th harmonic
13.9% of the rated current at the 9th harmonic
Beyond the 9th Harmonic the percentages of the fundamental current
through the 25th Harmonic shall be equal to the reciprocal of the odd
harmonic number involved times 1.25.
The FPType FHK20 series transformer is designed for 100% linear load
plus 125% non-linear load which can operate at a total (1 (pu) h)
K-factor load value of 20.
(D) 150% Non-Linear Load (K-30 Rating)
50.0% of the rated current at the 3rd harmonic
30.0% of the rated current at the 5th harmonic
21.4% of the rated current at the 7th harmonic
16.7% of the rated current at the 9th harmonic
Beyond the 9th Harmonic the percentages of the fundamental current
through the 25th Harmonic shall be equal to the reciprocal of the odd
harmonic number involved times 1.50.
The FPType FHK30 series transformer is designed for 100% linear load
plus 150% non-linear load which can operate at a total (1 (pu) h)
K-factor load value of 30.
Note: In these examples the amount of non-linear load specified, the
percentage of fundamental current, and the percentages of harmonic
factor are arbitrary values; actual values may vary. (Consult
manufacturer for your specific application or current values for each
harmonic.)
Transformers shall be sized to account for harmonic non-linear loads of
50% minimum (K-4), 100% (K-13), 125% (K-20), 150% (K-30).
The neutral connection shall be sized at 200% of the current rating of
the phase connections.
The conductors of the transformer winding shall be sized to handle
circulation of 3rd harmonic current and not exceed the rated temperature
rise.
Transformers shall be capable of operating within the specified
temperature rise while supplying 100% of the 60 Hertz fundamental rated
current values plus the following harmonics as calculated by ANSI/IEEE
57.110-1986.
K-Factor Transformer Ratings
The K-Factor rating assigned to a transformer and marked on the
transformer case in accordance with the listing of Underwriters
Laboratories, is an index of the transformer’s ability to supply
harmonic content in its load current while remaining within its
operating temperature limits. A specific K-factor rating indicates a
transformer can supply its rated KVA load output to a load of specified
amount of harmonic content. At present, industry literature and
commentary refers to a limited number of K-factor ratings: K-1, K-4,
K-9, K-12, K-20, K-30, and K-40. In theory, a transformer could be
designed for other K-factor ratings in-between those values, as well as
for higher values. The commonly referenced ratings calculated according
to ANSI/IEEE C57.110-1986 are as follows:
K-1: This is the rating of any conventional transformer that has
been designed to handle only the heating effects of eddy currents and
other losses resulting from 60 Hertz, sine-waves current loading on the
transformer. Such a unit may or may not be designed to handle the
increased heating of harmonics in its load current.
K-4: A transformer with this rating has been designed to supply
rated KVA, without overheating, to a load made-up of 100% of the normal
60 Hertz, sine-wave, fundamental current plus: 16% of the fundamental as
3rd harmonic current; 10% of the fundamental as 5th; 7% of the
fundamental as 7th; 5.5% of the fundamental as 9th; and smaller
percentages through the 25th harmonic. The “4” indicates its ability to
accommodate four times the eddy current losses of a K-1 transformer.
K-9: A K-9 transformer can accommodate 165% of the harmonic
loading of a K-4 rated transformer.
K-13: AK-13 transformer can accommodate 200% of the harmonic
loading of a K-4 rated transformer.
K-20, K-30, K-40: The higher number of each of these K-factor
ratings indicates ability to handle successively larger amounts of
harmonic load content with overheating.
Triplen Harmonics
Triplen harmonic currents are phase currents which flow from each of the
phases into the fourth wire neutral and have frequencies in integer
multiples of three times the 60 hertz base frequency (180 Hz, 360Hz,
540Hz, etc). At each of these third multiple triplen frequencies, these
triplen phase currents are in phase with each other and when flowing in
the neutral as zero sequence currents, are equal to three times their
RMS phase values.
In a 3-phase, 4-wire system, single-phase line-to-neutral currents, flow
in each phase conductor and return in the common neutral. Since the
three 60 hertz currents are separated by 120 degrees, when balanced they
cancel each other. The measured resultant current is equal to zero.
Theory also states that for even harmonics, starting with the second
order, when balanced the even harmonic will cancel in the common
neutral. Other odd harmonics add in the common neutral, but their
magnitude is considerable less than triplens. The RMS value of the total
current is the square root of the RMS value of the individual currents
squared.
The UL Approach for Transformers Supplying
Non-Sinusoidal Loads
A. A transformer intended for use with loads drawing non-sinusoidal
currents shall be marked “Suitable for non-sinusoidal current load with
K-factor not to exceed x. (x= 4, 9, 13, 20, 30, 40 or 50)
B. Formulas to determine eddy losses and total losses where the
transformer load losses (PLL) are to be determined as follows:
PLL = PDC (1+K(PEC))
Where:
PDC = the total 1 R losses
K= the K-factor rating at the transformer (4,9,13,20,30,40 or 50)
PEC = assumed eddy current losses calculated as follows:
PAC-PDC for transformers rated
PDC 300 KVA or
less, and
C (PAC-PDC) for transformers rated
PDC
4 more than 300 KVA
In which:
PAC = the impedance loss
C=0.7 for transformers having a turn ratio greater than 4:1 and having
one or more windings with a current rating greater than 1000 amperes, or
C=0.6 for all other transformers.
PDC4 = the 1 R losses for the inner winding
The impedance losses and the FR losses shall be determined in accordance
with the Test Code for Dry Type Distribution and Power Transformers,
ANSI/IEEE C57.12.91-1979.
DC Components of Load Current
As stated in ANSI/IEEE C57.110-1986
Harmonic load currents may be accompanied by DC components in the load
current, which are frequently caused by the loss of a diode in a
rectifier circuit. A DC component of load current will increase the
transformer core less slightly, and may increase the magnetizing current
and audible sound level.
Relatively small DC components (up to the RMS magnitude of the
transformer excitation current at rated voltage) are expected to have no
significant effect on the load carrying capability of a transformer
determined by this recommended practice. Higher DC load current
components may adversely affect transformer capability and must be
corrected by the user.
Harmonic currents flowing through transformer leakage impedance and
through system impedance may also produce some small harmonic distortion
in the voltage waveform at the transformer terminals. Such voltage
harmonics may cause extra harmonic losses in the transformer core.
However, operating experience has indicated that core temperature rise
usually will not be the limiting parameter for determination of safe
magnitudes of non-sinusoidal load currents.
Noise Isolation Transformer
The Noise Isolation Transformer suppresses common mode noise by
introducing a grounded shield between its primary and secondary
windings. The grounded shield provides a low impedance path to ground by
capacitive coupling, which prevents unwanted high frequency signals
contained in the source voltage from reaching the transformer secondary.
The grounded shield between the primary and secondary windings is called
an electrostatic shield. This shield does not perform any function with
regard to harmonic current or voltage distortion wave forms. However,
the shield is extremely valuable in protecting sensitive equipment from
common-mode electrical noise and transients generated on the line side
of the transformers.
The ration of the common mode noise attenuation (CMA) on the input to
that of the output of the transformer is expressed in decibels as shown
in Equation 3. An isolation transformer with an electrostatic shield can
have a ratio of input noise voltage (VIN) to output noise voltage (VOUT)
within the range of 10:1 to 1000:1 or even higher.
Federal Pacific Type DIT Drive Isolation Transformers are designed to
meet the requirements of SCR controlled, variable speed motor drives.
They are specifically constructed to withstand the mechanical forces
associated with SCR drive duty cycles and to isolate the source voltage
circuit from low frequency noise generated from SCR voltage spikes and
transient feedback. Whereas the electrostatic shielded transformer
attenuates higher frequency noise in the 10kHz – 100 kHz range.
Multiplying Effect of Cascading Shielded Transformers
Having the presence of an upline transformer with an electrostatic
shield may mean that other shielded transformers would not be required
in the system. However, if a shielded transformer feeds another shielded
transformer, there is an effect of the attenuation ratio multiplying. If
the attenuation ratio is 100:1 in each of the transformers, the total
attenuation will be 100x100=10,000:1. Obviously, cascading inherently
multiplies the attenuation effectiveness of shielded transformers. The
term cascading means that two or more transformers are connected in
series on the same system.
Estimating K-Factor Loads
For the most part, each designer or installer must make his/her own
decision regarding what K-factor to assign to any load or load category.
The following is intended to assist in that determination be presenting
what we believe are realistic, yet conservative, K-factors for a number
of loads and load categories based on their relative harmonic producing
capabilities.
Calculating K-Factor Loads
1. List the KVA value for each load category to be supplied. Next,
assign an ILK value that corresponds to the relative level of harmonics
drawn by each type of load.
2. Multiply the KVA of each load times the ILK rating that corresponds
to the assigned K-factor rating. This result is an indexed KVA-1LK
value:
KVA x ILK = KVA – ILK
3. Tabulate the total connected load KVA for all load categories to be
supplied.
4. Next, add-up the KVA ILK values for all loads or load categories to
be supplied by the transformer.
5. Divide the grand total KVA-ILK value by the total KVA load to be
supplied. This will give an average ILK for that combination of loads.
(Total KVA-ILK) divided by (Total KVA) = average ILK
SELECTION CHARTS
TYPE FHK-K-FACTOR DRY-TYPE TRANSFORMERS
K-FACTOR RATED - 80 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ
|
Kva |
Catalog Number
|
| 15 |
T4T15BK4E |
| 30 |
T4T30BK4E |
| 45 |
T4T45BK4E |
| 75 |
T4T75BK4E |
| 112.5 |
T4T112BK4E |
| 150 |
T4T150BK4E |
| 225 |
T4T225BK4E |
| 300 |
T4T300BK4E |
| 500 |
T4T500BK4E |
K-FACTOR RATED - 80 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD
|
Kva |
Catalog Number
|
| 15 |
T4T15BSK4E |
| 30 |
T4T30BSK4E |
| 45 |
T4T45BSK4E |
| 75 |
T4T75BSK4E |
| 112.5 |
T4T112BSK4E |
| 150 |
T4T150BSK4E |
| 225 |
T4T225BSK4E |
| 300 |
T4T300BSK4E |
| 500 |
T4T500BSK4E |
K-FACTOR RATED - 80 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD COPPER
|
Kva |
Catalog Number
|
| 15 |
T4T15BCSK4E |
| 30 |
T4T30BCSK4E |
| 45 |
T4T45BCSK4E |
| 75 |
T4T75BCSK4E |
| 112.5 |
T4T112BCSK4E |
| 150 |
T4T150BCSK4E |
| 225 |
T4T225BCSK4E |
| 300 |
T4T300BCSK4E |
K-FACTOR RATED - 80 DEGREES C - THREE PHASE -K4
480-240/120, 60HZ LT (LIGHTING TAP)
|
Kva |
Catalog Number
|
| 15 |
T43T15BK4E |
| 30 |
T43T30BK4E |
| 45 |
T43T45BK4E |
| 75 |
T43T75BK4E |
| 112.5 |
T43T112BK4E |
| 150 |
T43T150BK4E |
| 225 |
T43T225BK4E |
| 300 |
T43T300BK4E |
K-FACTOR RATED - 80 DEGREES C - THREE PHASE -K4
480-240/120, 60HZ LT (LIGHTING TAP) ELECTROSTATICALLY
SHIELD
|
Kva |
Catalog Number
|
| 15 |
T43T15BSK4E |
| 30 |
T43T30BSK4E |
| 45 |
T43T45BSK4E |
| 75 |
T43T75BSK4E |
| 112.5 |
T43T112BSK4E |
K-FACTOR RATED - 115 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ
|
Kva |
Catalog Number
|
| 15 |
T4T15FK4E |
| 30 |
T4T30FK4E |
| 45 |
T4T45FK4E |
| 75 |
T4T75FK4E |
| 112.5 |
T4T112FK4E |
| 150 |
T4T150FK4E |
| 225 |
T4T225FK4E |
| 300 |
T4T300FK4E |
| 500 |
T4T500FK4E |
K-FACTOR RATED - 115 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD
|
Kva |
Catalog Number
|
| 15 |
T4T15FSK4E |
| 30 |
T4T30FSK4E |
| 45 |
T4T45FSK4E |
| 75 |
T4T75FSK4E |
| 112.5 |
T4T112FSK4E |
| 150 |
T4T150FSK4E |
| 225 |
T4T225FSK4E |
| 300 |
T4T300FSK4E |
| 500 |
T4T500FSK4E |
K-FACTOR RATED - 115 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD COPPER
|
Kva |
Catalog Number
|
| 15 |
T4T15FCSK4E |
| 30 |
T4T30FCSK4E |
| 45 |
T4T45FCSK4E |
| 75 |
T4T75FCSK4E |
| 112.5 |
T4T112FCSK4E |
| 150 |
T4T150FCSK4E |
| 225 |
T4T225FCSK4E |
| 300 |
T4T300FCSK4E |
K-FACTOR RATED - 115 DEGREES C - THREE PHASE -K4
480-240/120, 60HZ LT (LIGHTING TAP)
|
Kva |
Catalog Number
|
| 15 |
T4T15FK4E |
| 30 |
T4T30FK4E |
| 45 |
T4T45FK4E |
| 75 |
T4T75FK4E |
| 112.5 |
T4T112FK4E |
| 150 |
T4T150FK4E |
| 225 |
T4T225FK4E |
| 300 |
T4T300FK4E |
K-FACTOR RATED - 115 DEGREES C - THREE PHASE -K4
480-240/120, 60HZ LT (LIGHTING TAP) ELECTROSTATICALLY
SHIELD
|
Kva |
Catalog Number
|
| 15 |
T4T15FSK4E |
| 30 |
T4T30FSK4E |
| 45 |
T4T45FSK4E |
| 75 |
T4T75FSK4E |
| 112.5 |
T4T112FSK4E |
| 150 |
T4T150FSK4E |
| 225 |
T4T225FSK4E |
| 300 |
T4T300FSK4E |
K-FACTOR RATED - 150 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ
|
Kva |
Catalog Number
|
| 15 |
T4T15K4E |
| 30 |
T4T30K4E |
| 45 |
T4T45K4E |
| 75 |
T4T75K4E |
| 112.5 |
T4T112K4E |
| 150 |
T4T150K4E |
| 225 |
T4T225K4E |
| 300 |
T4T300K4E |
| 500 |
T4T500K4E |
| 750 |
T4T500K4E |
K-FACTOR RATED - 150 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD
|
Kva |
Catalog Number
|
| 15 |
T4T15SK4E |
| 30 |
T4T30SK4E |
| 45 |
T4T45SK4E |
| 75 |
T4T75SK4E |
| 112.5 |
T4T112SK4E |
| 150 |
T4T150SK4E |
| 225 |
T4T225SK4E |
| 300 |
T4T300SK4E |
| 500 |
T4T500SK4E |
| 750 |
T4T500SK4E |
K-FACTOR RATED - 150 DEGREES C - THREE PHASE -K4
480-208Y/120, 60HZ ELECTROSTATICALLY SHIELD, COPPER
|
Kva |
Catalog Number
|
| 15 |
T4T15CSK4E |
| 30 |
T4T30CSK4E |
| 45 |
T4T45CSK4E |
| 75 |
T4T75CSK4E |
| 112.5 |
T4T112CSK4E |
| 150 |
T4T150CSK4E |
| 225 |
T4T225CSK4E |
| 300 |
T4T300CSK4E |
| 500 |
T4T500CSK4E |
K-FACTOR RATED - 150 DEGREES C - THREE PHASE -K4
480-240/120, LT (LIGHTING TAP)
|
Kva |
Catalog Number
|
| 15 |
T43T15K4E |
| 30 |
T43T30K4E |
| 45 |
T43T45K4E |
| 75 |
T43T75K4E |
| 112.5 |
T43T112K4E |
| 150 |
T43T150K4E |
| 225 |
T43T225K4E |
| 300 |
T43T300K4E |
K-FACTOR RATED - 150 DEGREES C - THREE PHASE -K4
480-240/120, LT (LIGHTING TAP) ELECTROSTATICALLY SHIELD
|
Kva |
Catalog Number
|
| 15 |
T43T15SK4E |
| 30 |
T43T30SK4E |
| 45 |
T43T45SK4E |
| 75 |
T43T75SK4E |
| 112.5 |
T43T112SK4E |
| 150 |
T43T150SK4E |
FEDERAL PACIFIC ALSO HAS K-13 AND K-20 CONSULT MANUFACTURER
Power Transformer Information:
|
 
Power Transformer Types
 |
Step Up and Step Down Transformers
to Power transformers to step-up ( raise) or step-down (lower) the
electrical voltage.
|
 |
Isolation Transformers
allows signal or power to be taken from one device and fed into
another without electrically connecting the two.
|
 |
Toroidal Transformers
are devices that transfer electrical energy from one electric
circuit to another, without changing the frequency, by
electromagnetic induction.
|

|
Custom
Transformers
are designed to meet certain performance specifications and size
requirement that you require. There is a wide range of custom
transformer types.
|

|
Buck Boost Transformers
is a ideal solution for changing line voltage by small amounts.
Often used to buck (lower), or boost (raise) the voltage from 208v
to 240v for lighting applications.
|

|
Pole Mounted Transformers
are mounted to poles for overhead electrical lines. Used in various applications.
Are available in single phase or three phase transformers.
|

|
Medium Voltage Transformers
are used with a medium range of voltages. They come in a full
range from liquid-filled, convention dry type as well as cast coil.
|
 |
Pad Mounted Transformers
are a excellent choice for commercial and industrial such as
manufacturing facilities, refineries, office buildings, schools,
hospitals, restaurants, and retail stores. They come in various
sizes and can be used underground as well.
|
 |
High
Voltage Transformers
typically these voltage transformers are used in power transmission
applications. High voltage transformers are also used in microwave.
|
|
- ACME Transformers
- With Acme Electric being in business
over 80 years, they have always believed in offering there customers superior service, quality and technical expertise in the
transformer market.
-
AMVECO Transformers -
AMVECO designs and manufactures toroids
transformers, current transformers, and auto transformers. Most
AMVECO products are custom designed utilizing their state-of-art proprietary
CAD programs. The AMVECO engineers can quickly generate designs in a
matter of hours, if needed.
-
Federal Pacific Transformers -
Federal Pacific is a division of Electro- Mechanical Corporation, a
privately held, American owned company founded in 1958. Federal
pacific offers dry-type transformers from .050 KVA through 10,000
KVA single and three phase, up to 34.5 KV, 150 KV BIL with UL
approval through 15 KV.
-
Marcus Transformer - Ever since they opened their doors for business a half a century ago,
they have been a leader in innovative transformer design. As a
family-owned company they are proud of the reputation they have
earned for making quality-built transformers that deliver
exceptional performance and savings.
-
Hammond Transformers - Hammond Manufacturing was founded in 1917 in Guelph, Ontario,
Canada. In the last 3 decades it has expanded to the US and the
international markets offering many types of power transformers.
- TEMCo Transformers
- TEMCo Transformer, a family-owned business which has been
manufacturing and distributing electrical products since
1968. They focus on transformers that significantly
reduce power consumption over 30 percent compared to competitive
makes.
- GE Transformers - GE has been a key player in the energy industry for
more than a century. Since the installation of
their first steam turbine in 1901. They have become
number one provider of high-technology power generation
and distribution equipment.
-
Jefferson Electric Transformers - Jefferson Electric has
been a pioneer and innovator of magnetic products since 1915.
Jefferson broad line of dry-type transformers are backed by quality
assurance systems so stringent that each and every unit gets
thoroughly tested before it goes out there door.
-
More power transformer brands -
Check out more companies by clinking this link.
Power Transformer Types
-
Distribution Transformers - Distribution
transformers are generally used in electrical power
distribution and transmission power. This class of transformer has
the highest power, or volt-ampere ratings. and the highest
continuous voltage rating.
-
Substation Transformers -
Substation Transformers are large
devices which usually weigh tens of thousands of pounds. They are
filled with tens of thousands of gallons of heat transfer fluid.
Although they are typically 99.8% efficient in the transforming of
electricity from one voltage to another, processing hundreds of Mega
Volts-Amps of electricity force the liberation of hundreds of BTUs
per second.
-
Medical Grade Isolation
Transformer -
Medical Grade Transformers generally refer to the transformers
used in medical devices as well as hospital, biomedical and patient
care equipment. There are a number of strict safety rules,
guidelines and laws governing the design, construction and the test
of these transformers.
-
Drive Isolation Transformer -
They are used to isolate a drive from a main power line to
prevent the transmission of harmonics that the drives produce back
into the power line. They stop drive harmonics from disrupting
computers and other sensitive equipment.
-
Toroidal Transformers -
Toroidal Transformers are more efficient than the cheaper laminated EI types of similar power level. Some of the advantages are smaller
size, lower weight, less mechanical hum, (making them superior in
audio amplifier), low-off-load loss.
|
-
Step-Up Transformers - A Step-Up Transformer is one whose
secondary voltage is greater than its primary voltage.
This kind of transformer "steps up" the voltage applied
to it. -
-
Step-Down Transformers
- A Step-Down Transformer is designed to reduce voltage from primary to
secondary.
They can range from sizes from .05 KVA to 500 KVA
-
Isolation Transformers -
An Isolation Transformer is a device that transfers energy from
the alternating current (AC) supply to an electrical or electronic
load. It isolates the windings to prevent transmitting certain
types of harmonics.
-
Buck Boost Transformers - Buck Boost
Transformers make small adjustments to the incoming voltage. They
are often used to change voltage from 208v to 240v for lighting
applications. Major advantages of Buck boost transformers
include; low cost, compact size and light weight.
-
High Voltage Transformer - There are many different types of
voltage transformers. A High Voltage Transformer operates with high
voltages. Typically, these voltage transformers are used in power
transmission applications, where voltages are high enough to present
a safety hazard.
-
Medium Voltage Transformers -
A Medium Voltage Transformer can be connected directly to a primary
distribution circuit and generally has the most load diversity.
These voltage transformers have installation practices that are
generally in accordance with application recommendations from the
Institute of Electrical and Electronic Engineers (IEEE).
-
Low Voltage Transformers
- A Low Voltage Transformer is an electrical device that transforms
120 volts (line voltage) into 12 volts or 24 volts (low voltage).
Some uses for low voltage transformer are in landscaping lighting.
-
Single Phase Transformers - In electrical engineering, single-phase electric power refers to the
distribution of electric power using a system in which all the
voltages of the supply vary in unison. Single-phase distribution is
used when loads are mostly lighting and heating, with few large
electric motors.
-
Three Phase Transformers - Three
Phase Transformers must have 3 coils or windings connected in
the proper sequence in order to match the incoming power and
therefore transform the power company voltage to the level of
voltage needed while maintaining the proper phasing or polarity.
-
Custom Transformers -
Custom Transformers are designed for a certain performance
specifications and size requirements. The company works with
your engineering specification.
-
Industrial Control Transformers -
Industrial Control Transformers are used to convert the
available supply voltage to the required voltage to supply
industrial control circuits and motor control loads.
-
Pad Mounted Transformers - Pad
Mounted Transformers are usually single phase, or three phase, and
used where safety is a main concern. Typical applications;
restaurant, commercial building, shopping mall, institutional.
-
Pole Mounted Transformers -
Pole Mounted Transformers are used for distribution in areas
with overhead primary lines. Outside a typical house one can see one
of these devices mounted on the top of an electrical pole.
-
Oil Filled Transformers -
Oil Filled Transformers are transformers that use insulating oil as
insulating materials. The oil helps cool the transformer.
Because it also provides part of the electrical insulation between
internal live parts, transformer oil must remain stable at high
temperatures over an extended period.
-
Dry Type Transformers - Dry-Type
Transformers are available for voltages up through 34.5 kV
(although the most common upper limit is 15) and KVA ratings up
through 10,000 (with 5000 as the usual limit). Dry-type use air as a
coolant, lowering health and environmentally concerns.
- Auto Transformers -
An Autotransformer is an electrical transformer with only one
winding. The winding has at least three electrical connection points
called taps. Autotransformers are frequently used in power
applications to interconnect systems operating at different voltage
classes, for example 138 kV to 66 kV for transmission. Another
application is in industry to adapt machinery built for 480 V
supplies to operate on the local 600 V supply.
- More power transformer types - Read further about additional
transformer types and their uses.
|
-
Electrical
Transformers -
Electrical Transformers are devices used to raise or lower the
voltage of alternating current. For instance, power is transported
over long distance in high voltage power lines and then transformers
lower the voltage so that the power can be used by a business or household.
-
Isolating
Transformers -
An Isolating Transformer is a transformer, often with
symmetrical windings, which is used to decouple two circuits.
An Isolation transformer allows an AC signal or power to be taken
from one device and fed into another without electrically connecting
the two circuits. Isolation transformers block transmission of DC
signals from one circuit to the other, but allow AC signals to pass.
-
Transmission
Power Lines - A Transmission Line is the material medium or structure that forms
all or part of a path from one place to another for directing the
transmission of energy, such as electromagnetic
or acoustic waves as well as electric power
transmission. Components of transmission lines include wires, coaxial
cables, dielectric slabs, option fibers,
electric power lines, and waveguides.
-
Transformer Voltage - The measure of the amount of force on a
unit charge because of the surrounding charge.
-
Transformer Phase - Most transformer are either single phase
or three phase.
-
Transformer Frequency -
The transformer cannot change the frequency of the supply. If the
supply is 60 hertz, the output will also be 60 hertz.
-
Transformer K Factor - Some transformers are now being offered
with a k-factor rating. This measure the transformer's ability to
withstand the heating effects of non-sinusoidal harmonic currents
produced by much of today's electronic equipment and certain
electrical equipment.
-
Primary Voltage - The coil winding that is directly connected
to the input power.
-
Secondary Voltage - The coil winding supplying the output
voltage.
-
Harmonic Cancellation -
Harmonic cancellation is performed with harmonic canceling
transformers also known as phase-shifting transformers. A harmonic
canceling transformer is a relatively new power quality product for
mitigating harmonic problems in electrical distribution systems.
This type of transformer has patented built-in electromagnetic
technology designed to remove high neutral current and the most
harmful harmonics from the 3rd through 21st.
- Weatherproof -
Enclosed transformers come with a weatherproof standard set by
NEMA.
- Epoxy Encapsulated -
A process in which a transformer or one of its components is
completely sealed with epoxy or a similar material. This process is
normally preferred when a unit might encounter harsh environmental
conditions.
-
More power transformer terms - Such as inductor, ground fault,
core saturation, current transformer, faraday shield, etc.
Related Transformer Products
-
Voltage Regulators - A
Voltage Regulator is an electrical regulator designed to
automatically maintain a constant voltage level.
It may use an electromechanical mechanism, or passive or active
electronic components. Depending on the design, it may be used to
regulate one or more AC or DC voltages.
-
AC Line Reactor -
AC Line Reactors is a three phase transformer used in
conjunction with AC variable frequency and DC motor drive.
They are a bi-directional protective filtering device.
-
Line Power Conditioners -
Power or Line Conditioners regulate, filter, and suppress noise in
AC power for sensitive computer and other solid state equipment.
-
DC Power Supplies -
Conversion of one form of electrical power to another desired
form and voltage. This typically involves converting 120 or 240 volt
AC supplied by a utility company to a well-regulated
lower voltage DC for electronic devices.
-
Rotary Phase Converters -
Rotary Phase Converters are commonly used in home or small
commercial or industrial settings. Rotary phase converters convert
single-phase power into three-phase power. This is a very
cost-effective way to power three-phase electric motors and other
three phase equipment.
-
Frequency Converters -
A Frequency Changer or Frequency Converter is an
electronic device that converts alternating current (AC) of one
frequency to alternating current of another frequency.
-
Voltage Converters -
A Voltage Converter changes the voltage of an electrical power
source and is usually combined with other components to create a
power supply.
-
Magnetic Motor Starters - Magnetic Motor Starters are
essentially heavy duty relays mounted in boxes, often equipped with
heater/thermal overloads matched to the motor they start.
-
Motor Starting Auto Transformers - An Auto
Transformer starter uses an auto transformer to reduce
the voltage applied to a motor during start. The auto transformer
may have a number of output taps and be set-up to provide a single
stage starter, or a multistage starter.
For an additional resource the
Best of Industry Web Directory
:
Electrical Power Transformer Directory section is quite useful. |