|
Federal Pacific Unit Substation Transformers
To Order Federal Pacific
Transformers We Recommend TEMCo
Ph:
1-800-613-2290
Or 1-510-490-2187
Link:
Power Transformer |
Unit Substation Transformers
5 and 15 KV Class
General Information
Description
Unit substation transformers are available in a wide variety of types
and ratings to provide reliable and versatile electrical distribution.
The changing needs and variable load densities of industrial and
commercial power systems create the need to locate transformers close to
the electrical center of the load – providing flexibility for change and
economical distribution of power.
Dry-type transformers are ideally suited for the applications. The
ventilated air-cooled construction eliminates the concern for
contamination and toxicity of cooling liquids. They do not require the
expensive vaults, fluid leakage containment provisions, or fire
protection systems needed for liquid filled units to satisfy National
Electric Code requirements.
Lower installed costs and minimum maintenance requirements make dry-type
substations transformers an ideal choice for new or existing
installations.
Transformers are available in three-phase ratings from 112-1/2 KVA to
10000 KVA. All standard primary and secondary voltage ratings are
provided to match load requirements to the distribution system.
Unites can be arranged for standard direct connection to high voltage
and low voltage distribution protective equipment or provided as
individual transformers.
Industry Standards
Unit substation transformers are designed and tested in accordance with
the following standards:
-
IEEE C57.12.01 General Requirements for
Distribution. Power and Regulating Transformers.
-
IEEE C57.12.91 Standard Test Code for Dry-Type
Distribution and Power Transformers.
-
NEMA 210-Secondary Unit Substations.
-
NEMA TR-27 Commercial Institutional and Industrial
Dry-Type Transformers.
Tested Performance
A high level of transformer reliability for trouble-free installation
and operation, all transformers manufactured are tested in accordance
with NEMA and IEEE Standards.
Ratio Test is performed on rated voltage connection and tap
connections to assure proper turns ratio on all connections.
Polarity Test and phase relation tests are made to ensure proper
polarity and marking because of their importance in paralleling or
banking two or more transformers,
No-load (excitation) Loss Test determines the losses of a
transformer which is excited at rated voltage and frequency, but which
is not supplying a load. Transformer excitation loss consists mainly of
the iron loss in the transformer core.
Load Loss Test determines the amount of losses in the transformer
when carrying full rated load. These losses consist primarily of PR
losses in the primary and secondary winding and ensure that
specifications of the transformer design are met.
Excitation Current Test determines the current necessary to
maintain transformer excitation.
Resistance Test is performed on the transformer windings and is
used to determine 1 R loss.
Impedance Test is made to insure that transformer design
standards are attained.
Dielectric Test (applied and induced potential) checks the
insulation and workmanship to demonstrate that the transformer has been
designed and manufactured to meet the insulation tests required by the
standards.
Applied Potential Test are made by impressing between windings
and between each winding and ground, a low frequency voltage in
accordance with the following:
Rated Voltage of
Winding, Volts |
Test Potential,
RMS kV |
| 250 |
4.0 |
| 600 |
4.0 |
| 2500 |
4.0 |
| 5000 |
10.0 |
| 8700 |
19.0 |
| 15000 |
34.0 |
Induced Potential Test call for over-exciting the transformer by
applying between the terminals on one winding a voltage of twice the
normal voltage developed in the winding for a period of 7200 cycles.
Partial Discharge (PD) is performed during the induced potential test.
Unit Substation Arrangements
Arrangements
Unit substation transformers meet a wide variety of application
requirements with the highest degree of service reliability. Substations
are coordinated, engineered electrical centers designed to safely step
down distribution voltage to utilization voltage. It usually supplies
secondary voltages ranging from 208Y/120 to 600 volts and primary
voltages of 2400 to 13800 volts. They typically provide power to
industrial plants, office buildings, commercial building, public
buildings, hospitals and schools. The form, rating, and characteristics
of unit substations and their transformers are determined by the design
of the electrical distribution system and the requirements of the
particular loads and installation conditions.
Incoming Line Air Interrupter Switch
The type AJII air interrupter switch, two position (open-close), three
pole with manually operated, stored-energy mechanism provides
quick-make, quick-break operation for disconnecting the transformer
incoming line. Utilized with power or current limiting fuses, the switch
provides safe, fast, and reliable protection for high voltage circuits.
The AJII switch is rated 600 or 1200 amp continuous, 600 or 1200 amp
load-break with a high fault closing capacity of 40,000 am asymmetrical.
The 1200A switch is available with 61,000 amp asymmetrical rating
(optional).
The switch compartment is bolted directly to the high voltage side of
the transformer section. Cable entrance can be at top or bottom for
either single or loop feed. Fuses, when specified, are located in a
compartment under the interrupter switch. A hinged door allows access to
fuses and is provided with a mechanical interlock to prevent the door
opening unless the switch is in the “open” position. Standard fuses,
when supplied, are the current limiting, non-disconnect type. Lightning
arresters and key interlocks are optionally available.
Incoming Line Terminal Compartment
When a disconnect or overcurrent device is not required as an integral
part of the lineup, an air-filled terminal compartment (ATC) is bolted
directly to the high voltage end of the transformer section. The
metal-enclosed terminal compartment matches the height and depth of the
transformer section and is provided with bolt-on end panels for
accessibility to terminal connections. The compartment can be arranged
for single or loop feed with potheads or clamp-type terminals for either
top or bottom cable entrance. Lightning arresters can be supplied when
required for protection against voltage surges.
Low Voltage Distribution Sections
A complete selection of distribution and protective equipment is
available to meet application requirements. Unit substation transformers
are arranged for direct connection to a variety of equipment including
low voltage draw-out switchgear, distribution switchboards, group
mounted power panel-boards and motor control centers.
For those applications where secondary distribution equipment is not
required, an outgoing air-filled terminal compartment (ATC) can be
provided for top or bottom cable entrance. The compartment bolts
directly to the transformer and have removable end panels for
accessibility. Provisions can also be made to accommodate busway.
Features of Typical 15 KV Substation Transformer
1. Round Cylindrical coils assure proper ventilation and provide
mechanical strength for fault stresses. The units are either barrel
wound or disc wound (depending on voltage) using aluminum conductor with
insulated coil supports.
2. Core structures are fabricated in a “stepped” configuration from
special high-grade, cold rolled, silicon steel. The steel laminations
are clamped at the top and bottom to absorb vertical stresses on the
core.
3. 220 degree C insulation systems using Nomex* paper and resin glass
laminates provides long operating life and quiet operation. The complete
core and coil assembly is impregnated with polyester varnish and oven
cured to make the assembly highly resistant to moisture.
4. High dielectric interphase barriers assure positive phase to phase
insulating characteristics.
5. High voltage tap connections are easily accessible by removal of
front panels. The centrally located taps are changed by moving jumpers
between connection points when the transformer is de-energized.
6. Rugged enclosure base with provisions for lifting, jacking, towing,
skidding or rolling for installation.
7. Rigidly braced low voltage bus bars arranged for proper electrical
connections to the transformer. The low voltage bus is equipped with
flexible connectors to the core and coil assembly to reduce transmission
of vibration to the connected equipment.
8. Diagrammatic nameplate provides complete rating and connection
information.
9. Vibration isolation pads isolate core and coil assembly from the base
structure to reduce sound levels.
10. Optional fan cooling equipment to provide an additional 33-1/3% KVA
capacity for units with self-cooled ratings of 300 KVA and above.
(Provisions for future forced air- cooling are provided as standard –
including sufficient current-carrying capacity on internal bus bars.)
Fans and controls can be installed at the factory or can be shipped for
installation at the jobsite.
Core and Coil Assembly
Core Construction
The transformer cores are made of high grade silicon electrical steel
laminations with high magnetic permeability. Precision steel cutting
machines are used to cut the steel laminations with precise squareness
and miter and to be free of burrs.
Laminations are hand stacked to computer generated specifications to
assure correct positioning for close fitting joints to minimize noise
and core loss. Each lamination has an insulating coating bonded to both
sides to minimize eddy-current losses.
The core legs are arranged in a “stepped” configuration to accommodate
the coils and to provide maximum cooling and strength. The completed
three-leg core assembly is rigidly clamped with steel members to prevent
movement and to provide support for the coils.
Coil Construction
Coils are precision wound in a circular configuration using aluminum
conductor material as standard. Copper conductors can also be provided
as an option.
On low voltage where possible, sheet-wound secondary windings are used.
The windings are separated by insulation layers and spacers. These sheet
windings offer the advantage of virtually eliminating axial short
circuit stresses.
Nomex insulated wire wound primary windings are placed directly over the
secondary windings with a suitable insulating barrier between the coils
consisting of spacers and sheet insulation applied to the proper
thickness. Primary windings may be random-wound or disc-wound depending
upon the design requirements. All coils are adequately braced for full
short circuit capability.
Assembly
The completed coil units are placed on the core legs. Top core yokes are
put into place and securely clamped. Electrical connections are made
using welded aluminum or brazes copper, to ensure reliable service.
Coils may be vacuum pressure impregnated, when specified. After
installation of the mounting hardware, the complete core and coil
assembly is submerses and impregnated with an insulating varnish. The
assembly is completely coated to provide moisture and dirt resistance as
well as high dielectric strength. After dipping, the varnish is fully
cured in a drying oven.
Completed core and coil assembles receive a final inspection and testing
prior to installation in the enclosure. When installed, vibration
isolation pads are provided to isolate the core and coil assembly from
the base structure. All structural parts are grounded to prevent induced
voltage buildup.
Construction
FB transformers utilize a 220 degree C insulation system that combines
inorganic materials and resins to provide a fire resistant, high
dielectric capability. All materials have been thoroughly tested and
proven with respect to their stability at required operating
temperatures.
The major components of the 220 degree C system include Nomex* paper for
conductor insulation plus resin-glass laminates, silicon rubber and
polyester varnish. The combination of materials is specifically chosen
to assure long operating life and quiet operations.
*Nomex is a Registered Trademark of Dupont Co.
Taps
Primary windings are furnished with full capacity tap connections to
provide adjustment to accommodate variations in the incoming high
voltage. All units include, as standard, two (2) 2-1/2% taps full
capacity above normal (FCAN) and two (2) 2-1/2% taps full capacity below
normal (FCBN).
The tap connections are located in a vertical arrangement on the side of
each coil. Accessible behind removable covers, the taps can easily be
changed by moving jumpers between connection points when the transformer
is de-energized.
Forced-Air Cooled System Operation
Unit substation transformers with self-cooled ratings of 300 KVA and
above can be supplied with fans and controls to obtain additional KVA
capacity. Forced circulation of air correctly applied permits the
self-cooled KVA rating of the transformer to be increased by an
additional 33-1/3%. (Class FA rating)
The winding temperature control panel is equipped with necessary
controls for the operation of the fans:
1. Winding temperature indicator
2. Fan position test switch
3. Temperature sensing device
4. Fuses
5. Green light (auxiliary power “On”)
6. Amber light (fan operation)
7. Red light (excessive temperature)
The winding temperature indicator is furnished with three (3) sets of
normally open contacts. Each contact closed as the average winding
temperature reaches factory preset temperature values.
Sequence of operation is as follows:
1. When the winding indicator reaches 190 degree C (based on 150 degree
C average winding temperature in a maximum 40 degree C ambient), the fan
relay is energized which closed the ran-relay contact. The fans operate
resulting in 33-1/3% additional KVA capacity.
2. Should the temperature increase to 200 degree C, the red light and
remote alarm (if connected) operate.
3. A further increase in winding temperature to 210 degree C will
operate contacts that can be used to trip the primary or secondary main
breaker.
General Specification Guide
The transformer shall be ventilated. Open, dry-type construction cooled
by the circulation of air through the windings. The unit shall be
mounted in an indoor or outdoor enclosure finished in the manufacturer’s
standard ANSI 61 light gray paint with provisions for direct connection
to the primary and secondary equipment as specified. The transformer
shall be designed, manufactured, and tested in accordance with the
applicable NEMA, ANSI, and IEEE standards. The facility in which the
transformers are manufactured shall be an ISO 9001:2000 registered
facility.
Insulation Materials
All insulations materials for the primary and secondary coil assembly
shall be rated for continuous 220 degree C total temperature (Class H).
Insulation on the rectangular wire conductor shall be Nomex* or
equivalent, which has a UL Listed 220 degree C insulation system having
suitable overlapping to keep dielectric volts/mil stress within limits
recommended by the insulation supplier. Layer insulation for LV strip
windings shall be Nomex* or equivalent, which is a UL Listed 220 degree
C insulation system having a thickness to keep volts/mil stress values
no higher than values recommended by the insulation supplier.
Core and Coil Assembly
The core shall be constructed of non-aging cold-rolled, high
permeability silicon steel. All core laminations shall be step-lap miter
cut, free of burrs and stacked without gaps. The core framing structure
shall be of rigid construction to provide full clamping pressure upon
the core and provide the support points for the coils. Butt lap
construction shall not be acceptable for the power ratings above 1000
KVA. The HV and LV coils shall be cylindrically wound (not rectangular)
as an assembly with the HV coil wound directly over the LV coil. Coils
shall be adequately braced for full short circuit capability to pass
shot circuit tests in accordance with IEEE C57.12.91.
VPI Process for transformer coils:
The coil assembly is baked for 2 hours at 190 degrees C to remove
moisture. Preheated coils are placed in a sealed VPI pressure/vacuum
tank and impregnated with a 100% solids varnish.
Final Dip and Bake
Upon completion of the VPI process of the coils and their assembly on
the core, the core top yokes are stacked, the core is clamped and all
necessary leads are welded (if aluminum) or brazed (if copper) to the LV
and MV bus components. At this time the complete core and coil assembly
is dipped into a soft solvent based varnish of Isonel 51 or equivalent
to provide a protective coating from oxidation for all bare metal parts
like core laminations and core clamping hardware. The varnish used for
this process must not be a hard varnish like a 100% solids material.
This core and coil assembly is then baked at the proper time and
temperature (usually 4-8 hours @ 175 degrees C) to cure all of the
varnish.
Transformer Enclosure and Base
The transformer base shall be welded construction and shall be
constructed to permit 4 point lifting using 1” diameter and 1-1/2” thick
lifting eyes along the base of the transformer. The enclosure shall
include provisions for rolling, skidding, lifting, and jacking for
installation.
Removable panels shall not exceed 70 pounds in weight and shall contain
suitably strong handles for lifting and placing. If installation space
is adequate, hinged doors may be provided, when specified.
The enclosure shall be constructed of heave gauge sheet steel equipped
with removable parts for access to the core and coils on the front and
rear. Ventilated openings shall be furnished to meet NEMA standards. The
cabinet metal must be at least 14 gauge thickness. Whenever the cabinet
must be outdoor (NEMA 3R) the ventilation openings must be constructed
as “back-to-back” channels. Paint for the transformer enclosure shall be
an ANSI-61 light gray color of a polyurethane powder coating that is
electrostatically applied conforming to UL 1332 specifications. For
installation areas within highly corrosive environments stainless steel
enclosures may be furnished as an option. Vibration dampening pads shall
be provided to isolate the core/coil assembly from the base structure.
High Voltage Taps
Each coil shall have taps at nominally rated voltage and additional 4
taps: 2-2-1/2% above and below rated nominal voltage. Tap leads shall be
terminated at the coils and equipped with provisions for changing taps
under de-energized conditions.
Sound Level
The transformer shall be designed to meet the sound level standards for
dry-type transformers as defined in IEEE C57.12.01-1998 or NEMA ST-20.
Forced-Air Cooling
When forced air cooling is specified, the forced-air cooling package
(fans and controller) shall be provided for automatically increasing the
self-cooled rating by 33-1.2%. The system shall contain 120 VAC single
phase fans and a control panel with indicating lights, temperature
indicator, fan position test switch, and alarm mode selector switch.
Accessories As Specified
Winding Temperature Controllers and Monitors shall be Qualitrol or
equivalent. Provisions for grounding shall be provided to be welded
Ground Pads or special termination hardware.
Final Tests
Final Test Reports in the proper IEEE format shall be furnished for each
unit, documenting the successful passing of all required tests.
Power Transformer Information:
|
 
Power Transformer Types
 |
Step Up and Step Down Transformers
to Power transformers to step-up ( raise) or step-down (lower) the
electrical voltage.
|
 |
Isolation Transformers
allows signal or power to be taken from one device and fed into
another without electrically connecting the two.
|
 |
Toroidal Transformers
are devices that transfer electrical energy from one electric
circuit to another, without changing the frequency, by
electromagnetic induction.
|

|
Custom
Transformers
are designed to meet certain performance specifications and size
requirement that you require. There is a wide range of custom
transformer types.
|

|
Buck Boost Transformers
is a ideal solution for changing line voltage by small amounts.
Often used to buck (lower), or boost (raise) the voltage from 208v
to 240v for lighting applications.
|

|
Pole Mounted Transformers
are mounted to poles for overhead electrical lines. Used in various applications.
Are available in single phase or three phase transformers.
|

|
Medium Voltage Transformers
are used with a medium range of voltages. They come in a full
range from liquid-filled, convention dry type as well as cast coil.
|
 |
Pad Mounted Transformers
are a excellent choice for commercial and industrial such as
manufacturing facilities, refineries, office buildings, schools,
hospitals, restaurants, and retail stores. They come in various
sizes and can be used underground as well.
|
 |
High
Voltage Transformers
typically these voltage transformers are used in power transmission
applications. High voltage transformers are also used in microwave.
|
|
- ACME Transformers
- With Acme Electric being in business
over 80 years, they have always believed in offering there customers superior service, quality and technical expertise in the
transformer market.
-
AMVECO Transformers -
AMVECO designs and manufactures toroids
transformers, current transformers, and auto transformers. Most
AMVECO products are custom designed utilizing their state-of-art proprietary
CAD programs. The AMVECO engineers can quickly generate designs in a
matter of hours, if needed.
-
Federal Pacific Transformers -
Federal Pacific is a division of Electro- Mechanical Corporation, a
privately held, American owned company founded in 1958. Federal
pacific offers dry-type transformers from .050 KVA through 10,000
KVA single and three phase, up to 34.5 KV, 150 KV BIL with UL
approval through 15 KV.
-
Marcus Transformer - Ever since they opened their doors for business a half a century ago,
they have been a leader in innovative transformer design. As a
family-owned company they are proud of the reputation they have
earned for making quality-built transformers that deliver
exceptional performance and savings.
-
Hammond Transformers - Hammond Manufacturing was founded in 1917 in Guelph, Ontario,
Canada. In the last 3 decades it has expanded to the US and the
international markets offering many types of power transformers.
- TEMCo Transformers
- TEMCo Transformer, a family-owned business which has been
manufacturing and distributing electrical products since
1968. They focus on transformers that significantly
reduce power consumption over 30 percent compared to competitive
makes.
- GE Transformers - GE has been a key player in the energy industry for
more than a century. Since the installation of
their first steam turbine in 1901. They have become
number one provider of high-technology power generation
and distribution equipment.
-
Jefferson Electric Transformers - Jefferson Electric has
been a pioneer and innovator of magnetic products since 1915.
Jefferson broad line of dry-type transformers are backed by quality
assurance systems so stringent that each and every unit gets
thoroughly tested before it goes out there door.
-
More power transformer brands -
Check out more companies by clinking this link.
Power Transformer Types
-
Distribution Transformers - Distribution
transformers are generally used in electrical power
distribution and transmission power. This class of transformer has
the highest power, or volt-ampere ratings. and the highest
continuous voltage rating.
-
Substation Transformers -
Substation Transformers are large
devices which usually weigh tens of thousands of pounds. They are
filled with tens of thousands of gallons of heat transfer fluid.
Although they are typically 99.8% efficient in the transforming of
electricity from one voltage to another, processing hundreds of Mega
Volts-Amps of electricity force the liberation of hundreds of BTUs
per second.
-
Medical Grade Isolation
Transformer -
Medical Grade Transformers generally refer to the transformers
used in medical devices as well as hospital, biomedical and patient
care equipment. There are a number of strict safety rules,
guidelines and laws governing the design, construction and the test
of these transformers.
-
Drive Isolation Transformer -
They are used to isolate a drive from a main power line to
prevent the transmission of harmonics that the drives produce back
into the power line. They stop drive harmonics from disrupting
computers and other sensitive equipment.
-
Toroidal Transformers -
Toroidal Transformers are more efficient than the cheaper laminated EI types of similar power level. Some of the advantages are smaller
size, lower weight, less mechanical hum, (making them superior in
audio amplifier), low-off-load loss.
|
-
Step-Up Transformers - A Step-Up Transformer is one whose
secondary voltage is greater than its primary voltage.
This kind of transformer "steps up" the voltage applied
to it. -
-
Step-Down Transformers
- A Step-Down Transformer is designed to reduce voltage from primary to
secondary.
They can range from sizes from .05 KVA to 500 KVA
-
Isolation Transformers -
An Isolation Transformer is a device that transfers energy from
the alternating current (AC) supply to an electrical or electronic
load. It isolates the windings to prevent transmitting certain
types of harmonics.
-
Buck Boost Transformers - Buck Boost
Transformers make small adjustments to the incoming voltage. They
are often used to change voltage from 208v to 240v for lighting
applications. Major advantages of Buck boost transformers
include; low cost, compact size and light weight.
-
High Voltage Transformer - There are many different types of
voltage transformers. A High Voltage Transformer operates with high
voltages. Typically, these voltage transformers are used in power
transmission applications, where voltages are high enough to present
a safety hazard.
-
Medium Voltage Transformers -
A Medium Voltage Transformer can be connected directly to a primary
distribution circuit and generally has the most load diversity.
These voltage transformers have installation practices that are
generally in accordance with application recommendations from the
Institute of Electrical and Electronic Engineers (IEEE).
-
Low Voltage Transformers
- A Low Voltage Transformer is an electrical device that transforms
120 volts (line voltage) into 12 volts or 24 volts (low voltage).
Some uses for low voltage transformer are in landscaping lighting.
-
Single Phase Transformers - In electrical engineering, single-phase electric power refers to the
distribution of electric power using a system in which all the
voltages of the supply vary in unison. Single-phase distribution is
used when loads are mostly lighting and heating, with few large
electric motors.
-
Three Phase Transformers - Three
Phase Transformers must have 3 coils or windings connected in
the proper sequence in order to match the incoming power and
therefore transform the power company voltage to the level of
voltage needed while maintaining the proper phasing or polarity.
-
Custom Transformers -
Custom Transformers are designed for a certain performance
specifications and size requirements. The company works with
your engineering specification.
-
Industrial Control Transformers -
Industrial Control Transformers are used to convert the
available supply voltage to the required voltage to supply
industrial control circuits and motor control loads.
-
Pad Mounted Transformers - Pad
Mounted Transformers are usually single phase, or three phase, and
used where safety is a main concern. Typical applications;
restaurant, commercial building, shopping mall, institutional.
-
Pole Mounted Transformers -
Pole Mounted Transformers are used for distribution in areas
with overhead primary lines. Outside a typical house one can see one
of these devices mounted on the top of an electrical pole.
-
Oil Filled Transformers -
Oil Filled Transformers are transformers that use insulating oil as
insulating materials. The oil helps cool the transformer.
Because it also provides part of the electrical insulation between
internal live parts, transformer oil must remain stable at high
temperatures over an extended period.
-
Dry Type Transformers - Dry-Type
Transformers are available for voltages up through 34.5 kV
(although the most common upper limit is 15) and KVA ratings up
through 10,000 (with 5000 as the usual limit). Dry-type use air as a
coolant, lowering health and environmentally concerns.
- Auto Transformers -
An Autotransformer is an electrical transformer with only one
winding. The winding has at least three electrical connection points
called taps. Autotransformers are frequently used in power
applications to interconnect systems operating at different voltage
classes, for example 138 kV to 66 kV for transmission. Another
application is in industry to adapt machinery built for 480 V
supplies to operate on the local 600 V supply.
- More power transformer types - Read further about additional
transformer types and their uses.
|
-
Electrical
Transformers -
Electrical Transformers are devices used to raise or lower the
voltage of alternating current. For instance, power is transported
over long distance in high voltage power lines and then transformers
lower the voltage so that the power can be used by a business or household.
-
Isolating
Transformers -
An Isolating Transformer is a transformer, often with
symmetrical windings, which is used to decouple two circuits.
An Isolation transformer allows an AC signal or power to be taken
from one device and fed into another without electrically connecting
the two circuits. Isolation transformers block transmission of DC
signals from one circuit to the other, but allow AC signals to pass.
-
Transmission
Power Lines - A Transmission Line is the material medium or structure that forms
all or part of a path from one place to another for directing the
transmission of energy, such as electromagnetic
or acoustic waves as well as electric power
transmission. Components of transmission lines include wires, coaxial
cables, dielectric slabs, option fibers,
electric power lines, and waveguides.
-
Transformer Voltage - The measure of the amount of force on a
unit charge because of the surrounding charge.
-
Transformer Phase - Most transformer are either single phase
or three phase.
-
Transformer Frequency -
The transformer cannot change the frequency of the supply. If the
supply is 60 hertz, the output will also be 60 hertz.
-
Transformer K Factor - Some transformers are now being offered
with a k-factor rating. This measure the transformer's ability to
withstand the heating effects of non-sinusoidal harmonic currents
produced by much of today's electronic equipment and certain
electrical equipment.
-
Primary Voltage - The coil winding that is directly connected
to the input power.
-
Secondary Voltage - The coil winding supplying the output
voltage.
-
Harmonic Cancellation -
Harmonic cancellation is performed with harmonic canceling
transformers also known as phase-shifting transformers. A harmonic
canceling transformer is a relatively new power quality product for
mitigating harmonic problems in electrical distribution systems.
This type of transformer has patented built-in electromagnetic
technology designed to remove high neutral current and the most
harmful harmonics from the 3rd through 21st.
- Weatherproof -
Enclosed transformers come with a weatherproof standard set by
NEMA.
- Epoxy Encapsulated -
A process in which a transformer or one of its components is
completely sealed with epoxy or a similar material. This process is
normally preferred when a unit might encounter harsh environmental
conditions.
-
More power transformer terms - Such as inductor, ground fault,
core saturation, current transformer, faraday shield, etc.
Related Transformer Products
-
Voltage Regulators - A
Voltage Regulator is an electrical regulator designed to
automatically maintain a constant voltage level.
It may use an electromechanical mechanism, or passive or active
electronic components. Depending on the design, it may be used to
regulate one or more AC or DC voltages.
-
AC Line Reactor -
AC Line Reactors is a three phase transformer used in
conjunction with AC variable frequency and DC motor drive.
They are a bi-directional protective filtering device.
-
Line Power Conditioners -
Power or Line Conditioners regulate, filter, and suppress noise in
AC power for sensitive computer and other solid state equipment.
-
DC Power Supplies -
Conversion of one form of electrical power to another desired
form and voltage. This typically involves converting 120 or 240 volt
AC supplied by a utility company to a well-regulated
lower voltage DC for electronic devices.
-
Rotary Phase Converters -
Rotary Phase Converters are commonly used in home or small
commercial or industrial settings. Rotary phase converters convert
single-phase power into three-phase power. This is a very
cost-effective way to power three-phase electric motors and other
three phase equipment.
-
Frequency Converters -
A Frequency Changer or Frequency Converter is an
electronic device that converts alternating current (AC) of one
frequency to alternating current of another frequency.
-
Voltage Converters -
A Voltage Converter changes the voltage of an electrical power
source and is usually combined with other components to create a
power supply.
-
Magnetic Motor Starters - Magnetic Motor Starters are
essentially heavy duty relays mounted in boxes, often equipped with
heater/thermal overloads matched to the motor they start.
-
Motor Starting Auto Transformers - An Auto
Transformer starter uses an auto transformer to reduce
the voltage applied to a motor during start. The auto transformer
may have a number of output taps and be set-up to provide a single
stage starter, or a multistage starter.
For an additional resource the
Best of Industry Web Directory
:
Electrical Power Transformer Directory section is quite useful. |