Hammond Buck Boost Transformers
Why
Use Buck-Boost Transformers?
The advantages of using a buck-boost transformer over an equivalent
standard isolation transformer are as follows:
Advantages
1) Used in a variety of applications
2) Inexpensive
3) Smaller and lighter
4) More efficient
5) 5-10 times increase in kVA
Disadvantages
1) No circuit isolation
2) Cannot create a neutral
3) KVA and voltages do not match what’s
on the nameplate kVA and voltages.
Buck-Boost Application
Buck-boost transformers offer an economical solution to the adjustment
of line voltages that are slightly above or below normal. When a
buck-boost transformer is connected as an autotransformer, only a
portion of the load kVA is actually transformed. The majority of the
load kVA is passed directly through to the source. For this
reason a buck-boost transformer may be used to supply a much larger load
kVA than is indicated on the nameplate. Buck-boost transformers can be
used to adjust stable voltages only. Fluctuating line voltages should
be
regulated with a Line Voltage Conditioner.
Buck-boost transformers represent an economical way to both raise supply
voltage caused by line drop or equipment demand on the distribution
system, or lower voltage caused by increased system voltages due to
supply line adjustments. Some loads including lighting and resistive
loads require a stable supply to maintain
performance. The detrimental effects of incorrect supply line voltage
can cause equipment failure. Buck-boost
transformers can correct line voltage within 5 to 25% of nominal.
Steps for Selecting Buck-Boost Transformers
The following information is required before selecting a buck-boost
transformer:
(1) Line Voltage - The voltage that you want to buck (decrease)
or boost (increase). This can be
determined by measuring the supply line voltage with a voltmeter.
(2) Load Voltage - The voltage at which your equipment is
designed to operate. This is listed on the
nameplate of the load equipment.
(3) Load kVA or Load Amps - You do not need to know both - one or
the other is sufficient. This
information usually can be found on the nameplate of the equipment that
you want to operate. It is the
sum of all the equipment that represents the load.
(4) Frequency - The supply line frequency must be the same as the
equipment to be operated - either
50 or 60 Hertz.
(5) Phase - The supply line should be the same as the load -
either single or three phase.
Selection Chart
Single Phase - Group A
|
CATALOG NO. |
| QC05ERCB |
| QC10ERCB |
| QC15ERCB |
| QC20ERCB |
| QC25ERCB |
| QC35ERCB |
| QC50ERCB |
| QC75ERCB |
| Q1C0ERCB |
| Q1C5ERCF |
| Q002ERCF |
| Q003ERCF |
| Q005ERCF |
Single Phase - Group B Selection Chart
|
CATALOG NO. |
| QC05ESCB |
| QC10ESCB |
| QC15ESCB |
| QC20ESCB |
| QC25ESCB |
| QC35ESCB |
| QC50ESCB |
| QC75ESCB |
| Q1C0ESCB |
| Q1C5ESCF |
| Q002ESCF |
| Q003ESCF |
| Q005ESCF |
Single Phase - Group C Selection Chart
|
CATALOG NO. |
| QC05DTCB |
| QC10DTCB |
| QC15DTCB |
| QC20DTCB |
| QC25DTCB |
| QC35DTCB |
| QC50DTCB |
| QC75DTCB |
| Q1C0DTCB |
| Q1C5DTCF |
| Q002DTCF |
| Q003DTCF |
| Q005DTCF |
Three Phase - Group A Selection Chart
|
CATALOG NO. |
| QC05ERCB |
| QC10ERCB |
| QC15ERCB |
| QC20ERCB |
| QC25ERCB |
| QC35ERCB |
| QC50ERCB |
| QC75ERCB |
| Q1C0ERCB |
| Q1C5ERCF |
| Q002ERCF |
| Q003ERCF |
| Q005ERCF |
Three Phase - Group B Selection Chart
|
CATALOG NO. |
| QC05ESCB |
| QC10ESCB |
| QC15ESCB |
| QC20ESCB |
| QC25ESCB |
| QC35ESCB |
| QC50ESCB |
| QC75ESCB |
| Q1C0ESCB |
| Q1C5ESCF |
| Q002ESCF |
| Q003ESCF |
| Q005ESCF |
Three Phase - Group C Selection Chart
|
CATALOG NO. |
| QC05DTCB |
| QC10DTCB |
| QC15DTCB |
| QC20DTCB |
| QC25DTCB |
| QC35DTCB |
| QC50DTCB |
| QC75DTCB |
| Q1C0DTCB |
| Q1C5DTCF |
| Q002DTCF |
| Q003DTCF |
| Q005DTCF |
Group A
Primary Voltage 120/240 Secondary Voltage 12/24 -50/60 Hertz
| VA |
CATALOG NO. |
| 50 |
QC05ERCB |
| 100 |
QC10ERCB |
| 150 |
QC15ERCB |
| 200 |
QC20ERCB |
| 250 |
QC25ERCB |
| 350 |
QC35ERCB |
| 500 |
QC50ERCB |
| 750 |
QC75ERCB |
| 1000 |
Q1C0ERCB |
| 1500 |
Q1C5ERCF |
| 2000 |
Q002ERCF |
| 3000 |
Q003ERCF |
| 5000 |
Q005ERCF |
Group B
Primary Voltage 120/240 Secondary Voltage 16/32 -50/60 Hertz
| VA |
CATALOG NO. |
| 50 |
QC05ESCB |
| 100 |
QC10ESCB |
| 150 |
QC15ESCB |
| 200 |
QC20ESCB |
| 250 |
QC25ESCB |
| 350 |
QC35ESCB |
| 500 |
QC50ESCB |
| 750 |
QC75ESCB |
| 1000 |
Q1C0ESCB |
| 1500 |
Q1C5ESCF |
| 2000 |
Q002ESCF |
| 3000 |
Q003ESCF |
| 5000 |
Q005ESCF |
Group C
Primary Voltage 240/480 Secondary Voltage 24/48 -50/60 Hertz
| VA |
CATALOG NO. |
| 50 |
QC05DTCB |
| 100 |
QC10DTCB |
| 150 |
QC15DTCB |
| 200 |
QC20DTCB |
| 250 |
QC25DTCB |
| 350 |
QC35DTCB |
| 500 |
QC50DTCB |
| 750 |
QC75DTCB |
| 1000 |
Q1C0DTCB |
| 1500 |
Q1C5DTCF |
| 2000 |
Q002DTCF |
| 3000 |
Q003DTCF |
| 5000 |
Q005DTCF |
Buck-Boost Transformers - Questions &
Answers
1. What is a buck-boost transformer?
Buck-boost transformers are small single phase transformers designed to
lower (buck) or raise (boost) line
voltage from 5-20%. The most common applications for buck-boost
transformers include boosting 208 volts to
230 or 240 volts for air conditioning systems, boosting 110 to 120 volts
and 240 to 277 volts for lighting
applications, heating systems and induction motors of all types. Many
applications exist where supply voltages
are frequently above or below nominal.
Buck-boost transformers are conventional low voltage, single phase
distribution transformers, with standard
primary voltages of 120, 240 or 480 volts, and secondary voltages of 12,
16, 24, 32 or 48 volts. They are
available
in sizes ranging from 50 VA to 10,000 VA. The primary and secondary are
wired together to form a singlewinding
autotransformer. Utilizing the additive and subtractive polarity, small
amounts of voltage are
either added
or subtracted from a distribution circuit.
2. How does a buck-boost transformer differ from an isolating
transformer?
A buck-boost transformer is manufactured as an isolating transformer,
with separable primary and secondary,
and is shipped from the factory in that configuration. When the end user
at site connects it, the primary is
connected to the secondary changing the transformer’s electrical
characteristics to those of an autotransformer.
This provides the smaller voltage correction that is typical of
buck-boost. The primary and secondary windings
are no longer isolated as they are connected together.
3. What is the difference between a buck-boost transformer and an
autotransformer?
As noted above, when the primary and secondary are connected together to
buck or boost voltage, the
transformer becomes an autotransformer. If the connection between the
primary and secondary winding is not
made, then the unit remains as an isolation transformer.
Applications
4. Why are they used?
A buck-boost transformer is a simple and effective way of correcting
off-standard voltages. Electrical and
electronic equipment is designed to operate within a standard tolerance
of nominal supply voltages. When the
supply voltage is consistently too high or low - typically more than
10%, the equipment will operate below peak
efficiency.
5. Can buck-boost transformers be used to power low voltage circuits?
Installed as two-winding, isolation transformers, these units can be
used to power low voltage circuits
including control, lighting circuits, or other low voltage applications
that require 12, 16, 24, 32 or 48 volts output,
consistent with the secondary of these designs. The unit is connected as
an isolating transformer and the
nameplate kVA rating is the transformer’s capacity.
Operation and Construction
6. Why do buck-boost transformers have 4 windings?
A four winding buck-boost transformer with 2 primary and 2 secondary
windings can be connected eight different
ways to provide a multitude of voltages and KVA’s. This provides the
flexibility necessary for the broad variety of
applications. A two-winding transformer can only be connected in two
different ways.
7. Will a Buck-Boost transformer stabilize voltage?
Autotransformers will not stabilize supply line voltage. The output
voltage of an autotransformer is a function
of the input voltage. If the input voltage varies, then the output
voltage will also vary by the same percentage.
Load Data
8. Are there any restrictions on the type of load that can be
operated from a Buck-Boost transformer?
There are no restrictions as to application for Buck-Boost, including
single or three-phase motor loads.
9. As an Autotransformer, how can a Buck-Boost transformer supply kVA
power?
This is a function of adding voltage - a small amount of voltage is
added and a small amount of corresponding
power capacity is added as well. For example, if the transformer is
connected in such a way that 22 volts is
added to a 208 volt primary, a 230 volt output will result.
Using this example, the calculation for autotransformer kVA is as
follows:
kVA = Output Volts x Secondary Amps
1000
kVA = 230V x 41.67 Amps = 9.58 KVA
1000
10. How are single phase and three phase load amps and load kVA
calculated?
Single phase Amps = kVA x 1000
Three phase Amps = kVA x 1000
Volts
Volts x 1.73
Single phase kVA = Volts x Amps
Three phase kVA = Volts x Amps x 1.73
1000
1000
Three Phase
11. Can Buck-Boost transformers be used on three phase systems?
Interconnecting two or three single phase units will readily accommodate
three phase systems . The number of units
to be used in a three phase installation
depends on the number of wires in the supply line. If the three
phase
supply is 4-wire wye, then three buck-boost
transformers are required. If the three phase supply is 3-wire wye
(neutral not available), two buck-boost transformers
are needed.
12. Should Buck-Boost transformers be used to develop three phase 4
wire wye circuits from three phase 3 wire delta circuits?
No - a three-phase “wye” buck-boost transformer connection should be
used only on a 4-wire source of
supply. A delta to wye connection does not provide adequate current
capacity to accommodate unbalanced
currents flowing in the neutral wire of the 4-wire circuit.
13. Why isn’t a ‘closed delta’ Buck-Boost connection recommended?
This connection requires more kVA power than a “wye” or open delta
connection and phase shifting occurs
on the output. The closed delta connection is more expensive and
electrically inferior to other three phase connections.
Connection and Frequency
14. How do you know how to connect a Buck-Boost transformer?
A connection chart is provided with each unit that shows how to make the
corresponding connections.
These same charts are also shown in this section.
15. Can 60 Hertz Buck-Boost transformers be operated on 50 Hertz?
Due to ‘saturation’ of the core, 60 Hertz buck-boost transformers should
only be operated at 60 Hertz, and
not 50 Hertz. Units manufactured as 50 Hertz units will however, operate
at 60 Hertz.
Nameplate Data
17. Why are buck-boost transformers shipped from the factory
connected as isolating transformers, and not pre-connected
autotransformers?
The same 4-winding buck-boost transformer can be connected eight
different ways to provide a multitude
of voltage combinations. The correct connection can best be determined
by the user when assessing the supply
voltage at site.
18. Why is the isolation transformer kVA rating shown on the
nameplate instead of the autotransformer kVA rating?
Shipped as an isolating transformer, the nameplate is required to show
the performance characteristics
accordingly. Additionally, as an autotransformer, the eight different
combinations of voltages and kVA’s would be
impractical to list on the nameplate. A connection chart, listing the
various connections, is included with each unit.
Safety
19. Do Buck-Boost transformers present a safety hazard compared to
conventional autotransformers?
Buck-boost transformers only change voltage by a small amount, such as
208 to 240 volts. This small
increase does not represent a safety hazard. Conventional
autotransformers, manufactured as single winding
transformers, change much higher magnitudes of voltage, e.g. 480 to 240
volts. In a system where the line is
grounded, it is possible to have 480 volts to ground when the
expectations are that 240 volts is at the output. For
this reason, qualified personnel only should maintain conventional
autotransformers.
Sound Levels
20. How does the sound level differ between Buck-Boost and isolation
transformers?
Buck-boost transformers, connected as autotransformers, will be quieter
than an equivalent isolation transformer
capable of handling the same load. The isolation transformer would have
to be physically larger than the
buck-boost transformer, and smaller transformers are quieter than larger
ones. For example, a 10 kVA is 35 dba
and a 75 kVA is 50 dba.
Cost and Life Expectancy
21. How does the costs compare between a Buck-Boost transformer and
an Isolation transformer handling the same load?
For most buck-boost applications, the savings are about 75% compared to
the use of an isolation transformer
for the same application.
22. What is the life expectancy of a Buck-Boost transformer?
Buck-boost transformers have exactly the same life expectancy as other
dry-type transformers.
23. Buck-Boost transformers are almost always installed as
autotransformers. Does the National Electrical Code (NEC) permit the use
of autotransformers?
Autotransformers are very common and recognized by all the safety and
standard authorities. You can
refer to N.E.C. Article 450-4, “Autotransformers 600 Volts, Nominal, or
Less”, as a reference publication.
Item (a)
details overcurrent protection for an autotransformer and item (b)
covers an isolation transformer being field connected as an
autotransformer for a buck-boost application.
24. When a Buck-Boost transformer is connected as an autotransformer,
what is the procedure for determining the current rating of the
overcurrent protective device, such as the fuse or circuit breaker?
The NEC Article 450-4 outlines overcurrent protection for
autotransformers. It is reproduced as follows:
“NEC 450-4 - Autotransformers 600 Volts, Nominal, or Less
(a) Overcurrent Protection. Each autotransformer 600 volts, nominal, or
less shall be protected by an
individual overcurrent device installed in series with each ungrounded
input conductor. Such overcurrent device
shall be rated or set at not more than 125 percent of the rated full
load input current of the autotransformer. An
overcurrent device shall not be installed in series with the shunt
winding.
Exception: Where the rated input current of an autotransformer is 9
amperes or more and 125 percent of
this current does not correspond to a standard rating of a fuse or
non-adjustable circuit breaker; the next higher
standard rating described in our section shall be permitted. When the
rated input current is less than 9 amperes,
an overcurrent device rated or set at not more than 167 percent of the
input current shall be permitted.
(b) Transformer Field-Connected as an autotransformer. A transformer
field-connected as autotransformers
shall be identified for use at “elevated voltage”.
Example: A 1 kVA transformer, Catalog No. Q1C0ERCB, is rated 120
x 240 to 12 x 24 volts. It is to be connected
as an autotransformer to raise 208 to 230 volts single phase. When
connected as an autotransformer in
this application, the kVA rating is increased to 9.58 kVA, or 9,580 VA.
This is the rating to be used for determining
the full load input amps and the corresponding size of the overcurrent
protection device, either a fuse or breaker.
Full load input amps = 9,580 Volt Amps = 46 Amp, 208 Volts
When the full load current is greater than 9 amps, the overcurrent
protection device - usually a fuse or nonadjustable breaker, the current
rating can be up to 125 percent of the full load rating of the
autotransformer
input current. Max. current rating of the overcurrent device = 46 amps x
125% = 57.5 amps
The National Electrical Code, Article 450-4 (a) Exception, permits the
use of the next higher standard ampere
rating of the overcurrent device. This is shown in Article 240-6 of the
N.E.C.
Max. size of the fuse or circuit breaker = 60 amps
o
HAMMOND
INDUSTRIAL CONTROL TRANSFORMERS
o HAMMOND
BUCK BOOST TRANSFORMERS
o HAMMOND
LINE REACTOR
TRANSFORMERS
o
HAMMOND DRIVE ISOLATION TRANSFORMERS
o
HAMMOND MOTOR STARTING AUTO TRANSFORMERS
o
HAMMOND
LOW VOLTAGE LIGHTING TRANSFORMERS
o
HAMMOND GENERAL PURPOSE DISTRIBUTION TRANSFORMERS
o
HAMMOND K-FACTOR TRANSFORMERS
o
HAMMOND ENCAPSULATED TRANSFORMERS
o
HAMMOND
AUTOTRANSFORMERS
o
HAMMOND GENERAL PURPOSE MEDIUM VOLTAGE TRANSFORMERS
Power Transformer Information:
|