Hammond K-Factor Transformers
The use of electronic equipment has continued to proliferate in both
offices and industrial plants. These electronic devices are powered by
either switching power supplies or a rectifier circuit. Examples of
these devices
include computers, fax machines, copiers, printers, cash registers,
UPS’s and solid-state ballasts. They all contribute to the distortion of
the current waveform and the generation of Harmonics. Harmonics, in an
electrical system, are currents created by non-linear loads that
generate non-sinusoidal (non-linear) current waveforms. These current
and voltage waveforms operate on frequencies that are in multiples of
the fundamental 60 hertz frequency. That is, the fundamental frequency
is at 60 hertz, the 2nd harmonic is at 120 hertz frequency (60 x 2), the
3rd at 180 hertz, and so forth.
Harmonics are principally the by-product of switch-mode power supply
technology where AC is rectified to DC, and back again. In the process,
a capacitor is charged in the first half-cycle and then discharged in
the next
half-cycle, in supplying current to the load. This cycle is repeated.
This action of recharging causes AC current to
flow only during a portion of the AC voltage wave, in abrupt pulses.
These abrupt pulses distort the fundamental
wave shape causing distortion to the various harmonic frequencies.
Non-Linear Loads
Today, non-linear loads make up a large percentage of all electrical
demand. Rectified input, switching power supplies and electronic
lighting ballasts are the most common single phase non-linear loads.
Harmonic
currents and voltages produced by single phase, non-linear loads which
are connected phase-to-neutral in a three
phase four wire system, are third order, zero sequence harmonics (the
third harmonic and its odd multiples - 3rd,
9th, 15th, 21st, etc., phasors displaced by zero degrees). These third
order, zero sequence harmonic currents do
not cancel, but add up arithmetically on the neutral bus, creating a
primary source of excessive neutral current.
HPS Synergy Series
600V CLASS ENERGY EFFICIENT K-FACTOR TRANSFORMER
K-Factor
K-factor is defined as a ratio between the additional losses due to
harmonics and the eddy current losses at 60Hz. It is used to specify
transformers for non-linear loads. Transformers with a rated K-factor of
4, 7, 13, 20 and 30 are available. For balanced loading, a transformer
with a K-factor of 4 should be specified when no more than 50% of the
total load is non-linear. A transformer with K-factor 13 should be
specified when 100% of the load is non-linear.
Energy efficient general purpose distribution transformers, most
frequently used for applications such as
commercial or institutional buildings, will, by definition, supply
widely varied single phase loads as described.
Energy Efficient K-Factor transformers are energy efficient general
purpose transformers, but are designed to
tolerate the harmonic distortion associated with these loads.
Harmonics indicate their presence in a number of ways:
overheating
device malfunctions
telephone interference
equipment vibration
breakers tripping
In a 60 Hz power system, the fundamental and harmonic frequencies
are outlined in the table below.
| Fundamental |
60 Hz |
| 2nd Harmonic |
120 Hz |
| 3rd Harmonic |
180 Hz |
| 4th Harmonic |
240 Hz |
| 5th Harmonic |
300 Hz |
| 6th Harmonic |
360 Hz |
| 7th Harmonic |
420 Hz |
| 8th Harmonic |
480 Hz |
| 9th Harmonic |
540 Hz |
| 10th Harmonic |
600 Hz |
| 11th Harmonic |
660 Hz |
| 12th Harmonic |
720 Hz |
| 13th Harmonic |
780 Hz |
| 14th Harmonic |
840 Hz |
| 15th Harmonic |
900 Hz |
| 16th Harmonic |
9600 Hz |
| 17th Harmonic |
1020 Hz |
| 18th Harmonic |
1080 Hz |
| 19th Harmonic |
1140 Hz |
| 20th Harmonic |
1200 Hz |
| 21st Harmonic |
1260 Hz |
| 22nd Harmonic |
1320 Hz |
| 23rd Harmonic |
1380 Hz |
| 24th Harmonic |
1440 Hz |
| 25th Harmonic |
1500 Hz |
HPS Synergy (part number prefix nmt)
Energy efficient k-factor transformers are designed to tolerate heating
due to harmonics associated with non-linear
loads. Harmonics can indicate their presence in a number of ways:
overheating, device malfunctions; telephone
interference; equipment vibration; and breakers tripping.
• Meets TP1 and C802.2 efficiencies at 35% of rated load.
• Efficiencies are calculated under a linear load profile.
• Copper and Aluminum Available.
SELECTION CHARTS
HPS Synergy
ALUMINUM WOUND, SHIELDED, THREE PHASE
600V CLASS ENERGY EFFICIENT K-FACTOR TRANSFORMERS
K-FACTOR 4
COPPER WOUND, SHIELDED, THREE PHASE
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT04K015KBS |
| 30 |
NMT04K030KBS |
| 45 |
NMT04K045KBS |
| 75 |
NMT04K075KBS |
| 112.5 |
NMT04K112KBS |
| 150 |
NMT04K150KBS |
| 225 |
NMT04K225KBS |
| 300 |
NMT04K300KBS |
| 500 |
NMT04K500KBS |
| 750 |
NMT04K750KBS |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT04K015PBS |
| 30 |
NMT04K030PBS |
| 45 |
NMT04K045PBS |
| 75 |
NMT04K075PBS |
| 112.5 |
NMT04K112PBS |
| 150 |
NMT04K150PBS |
| 225 |
NMT04K225PBS |
| 300 |
NMT04K300PBS |
| 500 |
NMT04K500PBS |
| 750 |
NMT04K750PBS |
COPPER WOUND, SHIELDED, THREE PHASE
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT04K015KBKF |
| 30 |
NMT04K030KBKN |
| 45 |
NMT04K045KBK |
| 75 |
NMT04K075KBK |
| 112.5 |
NMT04K112KBK |
| 150 |
NMT04K150KBK |
| 225 |
NMT04K225KBK |
| 300 |
NMT04K300KBK |
| 500 |
NMT04K500KBK |
| 750 |
NMT04K750KBK |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT04K015PBKF |
| 30 |
NMT04K030PBKN |
| 45 |
NMT04K045PBK |
| 75 |
NMT04K075PBK |
| 112.5 |
NMT04K112PBK |
| 150 |
NMT04K150PBK |
| 225 |
NMT04K225PBK |
| 300 |
NMT04K300PBK |
| 500 |
NMT04K500PBK |
| 750 |
NMT04K750PBK |
ALUMINUM WOUND, SHIELDED, THREE PHASE
K-FACTOR 13
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT13K015KBS |
| 30 |
NMT13K030KBS |
| 45 |
NMT13K045KBS |
| 75 |
NMT13K075KBS |
| 112.5 |
NMT13K112KBS |
| 150 |
NMT13K150KBS |
| 225 |
NMT13K225KBS |
| 300 |
NMT13K300KBS |
| 500 |
NMT13K500KBS |
| 750 |
NMT13K750KBS |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT13K015PBS |
| 30 |
NMT13K030PBS |
| 45 |
NMT13K045PBS |
| 75 |
NMT13K075PBS |
| 112.5 |
NMT13K112PBS |
| 150 |
NMT13K150PBS |
| 225 |
NMT13K225PBS |
| 300 |
NMT13K300PBS |
| 500 |
NMT13K500PBS |
| 750 |
NMT13K750PBS |
COPPER WOUND, SHIELDED, THREE PHASE
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT13K015KBKF |
| 30 |
NMT13K030KBKN |
| 45 |
NMT13K045KBK |
| 75 |
NMT13K075KBK |
| 112.5 |
NMT13K112KBK |
| 150 |
NMT13K150KBK |
| 225 |
NMT13K225KBK |
| 300 |
NMT13K300KBK |
| 500 |
NMT13K500KBK |
| 750 |
NMT13K750KBK |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT13K015PBKF |
| 30 |
NMT13K030PBKN |
| 45 |
NMT13K045PBK |
| 75 |
NMT13K075PBK |
| 112.5 |
NMT13K112PBK |
| 150 |
NMT13K150PBK |
| 225 |
NMT13K225PBK |
| 300 |
NMT13K300PBK |
| 500 |
NMT13K500PBK |
| 750 |
NMT13K750PBK |
ALUMINUM WOUND, SHIELDED, THREE PHASE
600V CLASS ENERGY EFFICIENT K-FACTOR TRANSFORMERS
K-FACTOR 20
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT20K015KBS |
| 30 |
NMT20K030KBS |
| 45 |
NMT20K045KBS |
| 75 |
NMT20K075KBS |
| 112.5 |
NMT20K112KBS |
| 150 |
NMT20K150KBS |
| 225 |
NMT20K225KBS |
| 300 |
NMT20K300KBS |
| 500 |
NMT20K500KBS |
| 750 |
NMT20K750KBS |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT20K015PBS |
| 30 |
NMT20K030PBS |
| 45 |
NMT20K045PBS |
| 75 |
NMT20K075PBS |
| 112.5 |
NMT20K112PBS |
| 150 |
NMT20K150PBS |
| 225 |
NMT20K225PBS |
| 300 |
NMT20K300PBS |
| 500 |
NMT20K500PBS |
| 750 |
NMT20K750PBS |
COPPER WOUND, SHIELDED, THREE PHASE
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT20K015KBKF |
| 30 |
NMT20K030KBK |
| 45 |
NMT20K045KBK |
| 75 |
NMT20K075KBK |
| 112.5 |
NMT20K112KBK |
| 150 |
NMT20K150KBK |
| 225 |
NMT20K225KBK |
| 300 |
NMT20K300KBK |
| 500 |
NMT20K500KBK |
| 750 |
NMT20K750KBK |
600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
NMT20K015PBKF |
| 30 |
NMT20K030PBKN |
| 45 |
NMT20K045PBK |
| 75 |
NMT20K075PBK |
| 112.5 |
NMT20K112PBK |
| 150 |
NMT20K150PBK |
| 225 |
NMT20K225PBK |
| 300 |
NMT20K300PBK |
| 500 |
NMT20K500PBK |
| 750 |
NMT20K750PBK |
HPS SuperSynergy
600 VOLT CLASS ENERGY EFFICIENT K-FACTOR
TRANSFORMERS
K-Factor Transformer Efficiencies:
HPS SuperSynergy (part number prefix smt)
The HPS SuperSynergy energy efficient k-factor transformer exceeds
TP1/C802.2 efficiencies over a range of
linear loads. It will not only satisfy the necessity for running at
k-factor modern building load types, but in
addition, because of the increasing need for energy conservation, they
are much more efficient than that of our
standard energy efficient line. The HPS SuperSynergy will meet
TP1/C802.2 efficiencies under a non-linear load
profile of up to K20 at an operating range at 35%-65% of the rated load.
• Efficiency performance will be 25% better than TP1 and C802.2
standards when measured under a linear load
profile at an operating range from 35% to 65% of rated load.
• Efficiency will meet or exceed TP1 and C802.2 standards at an
operating range of 35%-65% of rated load
when measured under a non-linear load profile up to K20.
• Copper and Aluminum Available.
SELECTION CHARTS
ALUMINUM WOUND, SHIELDED, THREE PHASE K-FACTOR 13
208 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015BBS |
| 30 |
SMT13K030BBS |
| 45 |
SMT13K045BBS |
| 75 |
SMT13K075BBS |
| 112.5 |
SMT13K112BBS |
| 150 |
SMT13K150BBS |
| 225 |
SMT13K225BBS |
| 300 |
SMT13K300BBS |
| 500 |
SMT13K500BBS |
| 750 |
SMT13K750BBS |
208 Delta Primary Volts 480Y/277Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015BKS |
| 30 |
SMT13K030BKS |
| 45 |
SMT13K045BKS |
| 75 |
SMT13K075BKS |
| 112.5 |
SMT13K112BKS |
| 150 |
SMT13K150BKS |
| 225 |
SMT13K225BKS |
| 300 |
SMT13K300BKS |
| 500 |
SMT13K500BKS |
| 750 |
SMT13K750BKS |
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015KBS |
| 30 |
SMT13K030KBS |
| 45 |
SMT13K045KBS |
| 75 |
SMT13K075KBS |
| 112.5 |
SMT13K112KBS |
| 150 |
SMT13K150KBS |
| 225 |
SMT13K225KBS |
| 300 |
SMT13K300KBS |
| 500 |
SMT13K500KBS |
| 750 |
SMT13K750KBS |
480 Delta Primary Volts 480Y/277Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015KKS |
| 30 |
SMT13K030KKS |
| 45 |
SMT13K045KKS |
| 75 |
SMT13K075KKS |
| 112.5 |
SMT13K112KKS |
| 150 |
SMT13K150KKS |
| 225 |
SMT13K225KKS |
| 300 |
SMT13K300KKS |
| 500 |
SMT13K500KKS |
| 750 |
SMT13K750KKS |
600 Delta Primary Volts 208Y/120 Secondary Volts 60
Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015PBS |
| 30 |
SMT13K030PBS |
| 45 |
SMT13K045PBS |
| 75 |
SMT13K075PBS |
| 112.5 |
SMT13K112PBS |
| 150 |
SMT13K150PBS |
| 225 |
SMT13K225PBS |
| 300 |
SMT13K300PBS |
| 500 |
SMT13K500PBS |
| 750 |
SMT13K750PBS |
600 Delta Primary Volts 480Y/277Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015PKS |
| 30 |
SMT13K030PKS |
| 45 |
SMT13K045PKS |
| 75 |
SMT13K075PKS |
| 112.5 |
SMT13K112PKS |
| 150 |
SMT13K150PKS |
| 225 |
SMT13K225PKS |
| 300 |
SMT13K300PKS |
| 500 |
SMT13K500PKS |
| 750 |
SMT13K750PKS |
COPPER WOUND, SHIELDED, THREE PHASE
208 Delta Primary Volts 208Y/120 Secondary Volts 60
Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015BBK |
| 30 |
SMT13K030BBK |
| 45 |
SMT13K045BBK |
| 75 |
SMT13K075BBK |
| 112.5 |
SMT13K112BBK |
| 150 |
SMT13K150BBK |
| 225 |
SMT13K225BBK |
| 300 |
SMT13K300BBK |
| 500 |
SMT13K500BBK |
| 750 |
SMT13K750BBK |
208 Delta Primary Volts 480Y/277 Secondary Volts 60
Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015BKKN |
| 30 |
SMT13K030BKK |
| 45 |
SMT13K045BKK |
| 75 |
SMT13K075BKK |
| 112.5 |
SMT13K112BKK |
| 150 |
SMT13K150BKK |
| 225 |
SMT13K225BKK |
| 300 |
SMT13K300BKK |
| 500 |
SMT13K500BKK |
| 750 |
SMT13K750BKK |
480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015KBKN |
| 30 |
SMT13K030KBKN |
| 45 |
SMT13K045KBK |
| 75 |
SMT13K075KBK |
| 112.5 |
SMT13K112KBK |
| 150 |
SMT13K150KBK |
| 225 |
SMT13K225KBK |
| 300 |
SMT13K300KBK |
| 500 |
SMT13K500KBK |
| 750 |
SMT13K750KBK |
480 Delta Primary Volts 480Y/277Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015KKKN |
| 30 |
SMT13K030KKKN |
| 45 |
SMT13K045KKK |
| 75 |
SMT13K075KKK |
| 112.5 |
SMT13K112KKK |
| 150 |
SMT13K150KKK |
| 225 |
SMT13K225KKK |
| 300 |
SMT13K300KKK |
| 500 |
SMT13K500KKK |
| 750 |
SMT13K750KKK |
600 Delta Primary Volts 208Y/120 Secondary Volts 60
Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015PBKN |
| 30 |
SMT13K030PBKN |
| 45 |
SMT13K045PBK |
| 75 |
SMT13K075PBK |
| 112.5 |
SMT13K112PBK |
| 150 |
SMT13K150PBK |
| 225 |
SMT13K225PBK |
| 300 |
SMT13K300PBK |
| 500 |
SMT13K500PBK |
| 750 |
SMT13K750PBK |
600 Delta Primary Volts 480Y/277Secondary Volts 60 Hz
| KVA |
CATALOG NO. |
| 15 |
SMT13K015PKKN |
| 30 |
SMT13K030PKKN |
| 45 |
SMT13K045PKK |
| 75 |
SMT13K075PKK |
| 112.5 |
SMT13K112PKK |
| 150 |
SMT13K150PKK |
| 225 |
SMT13K225PKK |
| 300 |
SMT13K300PKK |
| 500 |
SMT13K500PKK |
| 750 |
SMT13K750PKK |
o
HAMMOND
INDUSTRIAL CONTROL TRANSFORMERS
o HAMMOND
BUCK BOOST TRANSFORMERS
o HAMMOND
LINE REACTOR
TRANSFORMERS
o
HAMMOND DRIVE ISOLATION TRANSFORMERS
o
HAMMOND MOTOR STARTING AUTO TRANSFORMERS
o
HAMMOND
LOW VOLTAGE LIGHTING TRANSFORMERS
o
HAMMOND GENERAL PURPOSE DISTRIBUTION TRANSFORMERS
o
HAMMOND K-FACTOR TRANSFORMERS
o
HAMMOND ENCAPSULATED TRANSFORMERS
o
HAMMOND
AUTOTRANSFORMERS
o
HAMMOND GENERAL PURPOSE MEDIUM VOLTAGE TRANSFORMERS
Power Transformer Information:
|