
Transformer Phase
In electrical engineering, single-phase electric power refers to the
distribution of electric power using a system in which all the voltages
of the supply vary in unison. Single-phase distribution is used when
loads are mostly lighting and heating, with few large electric motors.
To Order Power Transformers We Recommend TEMCo
Ph:
1-800-613-2290
Or 1-510-490-2187
Link:
Power Transformer |
The generation of AC electric power is commonly three phase, in which
the waveforms of three supply conductors are offset from one another by
120°. Standard frequencies are either 50 or 60 Hz.
A single-phase load may be powered from a three-phase distribution
system either by connection between a phase and neutral [120 V or 220
V], or by connecting the load between two phases [120 V and 120 V, the
total being 240 V or 220 V and 220 V, the total being 440 V]. The load
device must be designed for the voltage in each case.
For example, in places using a 415 volt 3 phase system, the
phase-to-neutral voltage is 240 volts, allowing lighting to be connected
phase-to ground and motors to be connected to all three phases.
In North America, a typical three-phase system will have 208 volts
between the phases and 120 volts between phase and ground. If heating
equipment designed for the 240-volt three-wire single phase system is
connected to two phases of a 208 volt supply, it will only produce 75%
of its rated heating effect. Single-phase motors may have taps to allow
their use on either 208 V or 240 V supplies.
On higher voltage systems (kilovolts) where a single phase transformer
is in use to supply a low voltage system the method of splitting seems
to vary by country. In North America the primary of the step-down
transformer is wired across a single high voltage feed wire and ground,
at least for smaller supplies . In Britain the step-down primary is
wired phase-phase.
Single-phase loads may be connected to a three-phase system, either by
connecting across two live conductors (a phase-to-phase connection), or
by connecting between a phase conductor and the system neutral, which is
either connected to the center of the Y (star) secondary winding of the
supply transformer, or is connected to the center of one winding of a
delta transformer. Single-phase loads should be distributed evenly
between the phases of the three-phase system for efficient use of the
supply transformer and supply conductors.
The line-to-line voltage of a three-phase system is 3 times the line to
neutral voltage. Where the line-to-neutral voltage is a standard
utilization voltage, (for example in a 240 V/415 V system) individual
single-phase utility customers or loads may each be connected to a
different phase of the supply. Where the line-to-neutral voltage is not
a common utilization voltage, for example in a 347/600 V system,
single-phase loads must be supplied by individual step-down
transformers. In multiple-unit residential buildings in North America,
lighting and convenience outlets can be connected line-to-neutral to
give the 120 V distribution voltage (115V utilization voltage), and
high-power loads such as cooking equipment, space heating, water
heaters, or air conditioning can be connected across two phases to give
208 V. This practice is common enough that 208 V single-phase equipment
is readily available in North America. Attempts to use the more common
120/240 V equipment intended for three-wire single-phase distribution
may result in poor performance since 240 V heating equipment will only
produce 75% of its rating when operated at 208 V.
No arrangement of transformers can convert a single-phase load into a
balanced load on a polyphase system. Single-phase power distribution is
used especially in rural areas, where the cost of a three-phase
distribution network is high and motor loads are small and uncommon. Two
phase power, meaning the simultaneous provision of sine wave and cosine
wave electricity (that is, 90 degrees out of phase) is no longer widely
used. But some people incorrectly describe split single phase services
as "two phase", when in fact such services are really still single phase
power.
Three-phase is a common method of electric power transmission. It is a
type of system used to power motors and many other devices.
Three phase systems may or may not have a neutral wire. A neutral wire
allows the three phase system to use a higher voltage while still
supporting lower voltage single phase appliances. In high voltage
distribution situations it is common not to have a neutral wire as the
loads can simply be connected between phases (phase-phase connection).
Three phase has properties that make it very desirable in electric power
systems. Firstly the phase currents tend to cancel one another (summing
to zero in the case of a linear balanced load). This makes it possible
to eliminate the neutral conductor on some lines. Secondly power
transfer into a linear balanced load is constant, which helps to reduce
generator and motor vibrations. Finally, three-phase systems can produce
a magnetic field that rotates in a specified direction, which simplifies
the design of electric motors. Three is the lowest phase order to
exhibit all of these properties. Most domestic loads are single phase.
Generally three phase power either does not enter domestic houses at
all, or where it does, it is split out at the main distribution board.
The three phases are typically indicated by colors which vary by
country.
Occasionally the advantages of three-phase motors make it
worthwhile to convert single-phase power to three phase. Small
customers, such as residential or farm properties may not have access to
a three-phase supply, or may not want to pay for the extra cost of a
three-phase service, but may still wish to use three-phase equipment.
Such converters may also allow the frequency to be varied allowing speed
control. Some locomotives are moving to multi-phase motors driven by
such systems even though the incoming supply to a locomotive is nearly
always either DC or single phase AC.
Because single-phase power is interrupted at each moment that the
voltage crosses zero but three-phase delivers power continuously, any
such converter must have a way to store energy for the necessary
fraction of a second.
One method for using three-phase equipment on a single-phase supply is
with a rotary phase converter, essentially a three-phase motor with
special starting arrangements and power factor correction that produces
balanced three-phase power. When properly designed these rotary
converters can allow satisfactory operation of three-phase equipment
such as machine tools on a single phase supply. In such a device, the
energy storage is performed by the mechanical inertia (flywheel effect)
of the rotating components.
A second method that was popular in the 1940s and 50s was a method that
was called the transformer method. In that time period capacitors were
more expensive relative to transformers. So an autotransformer was used
to apply more power through fewer capacitors. This method performs well
and does have supporters, even today. The usage of the name transformer
method separated it from another common method, the static converter, as
both methods have no moving parts, which separates them from the rotary
converters.
Another method often attempted is with a device referred to as a static
phase converter. This method of running three phase equipment is
commonly attempted with motor loads though it only supplies power and
can cause the motor loads to run hot and in some cases overheat. This
method will not work when any circuitry is involved such as cnc devices,
or in induction and rectifier type loads.
Some devices are made which create an imitation three-phase from
three-wire single phase supplies. This is done by creating a third "subphase"
between the two live conductors, resulting in a phase separation of 180°
− 90° = 90°. Many three-phase devices will run on this configuration,
but at lower efficiency.
Power Transformer Information:
|