
More Power Transformer Types
Below are a few additional different types of transformers.
Zigzag Transformer
A zigzag transformer is a special purpose transformer. It has primary
windings but no secondary winding. One application is to derive an earth
reference point for an ungrounded electrical system. Another is to
control harmonic currents.
To Order Power Transformers We Recommend TEMCo
Ph:
1-800-613-2290
Or 1-510-490-2187
Link:
Power Transformer |
Consider a three-phase Y (wye) transformer with an earth connection on
the neutral point. Cut each winding in the middle so that the winding
splits into two. Turn the outer winding around and rejoin the outer
winding to the next phase in the sequence (i.e. outer A phase connects
to inner B phase, outer B phase connects to inner C phase, and outer C
phase connects to inner A phase). This device is the zigzag transformer.
When a zigzag transformer is connected to a healthy electrical system,
negligible current flows in the connection between the zigzag's neutral
point and earth. By design, the magnetic fluxes in the split windings
cancel each other out. With negligible current flows in the neutral
under normal conditions, engineers typically elect to undersize the
transformer. A short time rating is applied (i.e. the transformer can
only carry full rated current for, say, 60 seconds).
If one phase of the delta faults to earth, the voltage applied to each
phase of the zigzag is no longer in balance. Fluxes in the windings no
longer oppose. Zero sequence (earth fault) current flows between the
zigzag’s neutral to the phase effected by the fault. Hence, the purpose
of a zigzag transformer, to provide a return path for earth faults on
delta-connected systems.
An application example: Occasionally engineers use a combination of Y (wye
or star), delta, and zigzag windings to achieve a vector phase shift.
For example, an electrical network may have a transmission network of
110/33 kV star/star transformers, with 33/11 delta/star for the high
voltage distribution network. If a transformation is required directly
between the 110/11 kV network the most obvious option is to use 110/11
kV star/delta. The problem is that the 11 kV delta no longer has an
earth reference point. Installing a zigzag transformer near the
secondary side of the 110/11 kV transformer provides the required earth
reference point.
Polyphase Transformers
For three-phase power, three separate single-phase transformers can be
used, or all three phases can be connected to a single polyphase
transformer. The three primary windings are connected together and the
three secondary windings are connected together. The most common
connections are Y-Δ, Δ-Y, Δ-Δ and Y-Y. A vector group indicates the
configuration of the windings and the phase angle difference between
them. If a winding is connected to earth (grounded), the earth
connection point is usually the center point of a Y winding. If the
secondary is a Δ winding, the ground may be connected to a center tap on
one winding (high leg delta) or one phase may be grounded (corner
grounded delta). A special purpose polyphase transformer is the zigzag
transformer. There are many possible configurations that may involve
more or fewer than six windings and various tap connections.
Resonant Transformers
A resonant transformer operates at the resonant
frequency of one or more of its coils and (usually) an
external capacitor. The resonant coil, usually the
secondary, acts as an inductor, and is connected in
series with a capacitor. When the primary coil is driven
by a periodic source of alternating current, such as a
square or Sawtooth wave at the resonant frequency, each
pulse of current helps to build up an oscillation in the
secondary coil. Due to resonance, a very high voltage
can develop across the secondary, until it is limited by
some process such as electrical breakdown. These devices
are used to generate high alternating voltages, and the
current available can be much larger than that from
electrostatic machines.
Other applications of resonant transformers are as coupling between
stages of a super heterodyne receiver, where the selectivity of the
receiver is provided by the tuned transformers of the
intermediate-frequency amplifiers.
A voltage-regulating transformer uses a resonant winding and allows part
of the core to go into saturation on each half-cycle of the alternating
current. This effect stabilizes the output of the regulating
transformer, which can be used for equipment that is sensitive to
variations of the supply voltage. Saturating transformers provide a
simple rugged method to stabilize an AC power supply. However, due to
the hysteresis losses accompanying this type of operation, efficiency is
low.
Current Transformers
Current transformers used in metering equipment for three-phase 400
ampere electricity supply a current transformer is a type of "instrument
transformer" that is designed to provide a current in its secondary
which is accurately proportional to the current flowing in its primary.
This accuracy is directly related to a number of factors including the
following: burden, rating factors, load, external electromagnetic field,
and temperature and physical CT configuration.
The burden in a CT metering circuit is essentially the amount of
impedance (largely resistive) present. Typical burden ratings for CTs
are B-0.1, B-0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a
burden rating of B-0.2 can tolerate up to 0.2Ω of impedance in the
metering circuit before its output current is no longer a fixed ratio to
the primary current. Items that contribute to the burden of a current
measurement circuit are switch blocks meters and intermediate
conductors. The most common source of excess burden in a current
measurement circuit is the conductor between the meter and the CT.
Oftentimes, substation meters are located significant distances from the
meter cabinets and the excessive length of small gauge conductor creates
a large resistance. This problem can be solved by using CT with 1 ampere
secondaries which will produce less voltage drop between a CT and its
metering devices.
Rating factor is a factor by which the nominal full load current of a CT
can be multiplied to determine its absolute maximum measurable primary
current. Conversely, the minimum primary current a CT can accurately
measure is "light load," or 10% of the nominal current (there are,
however, special CTs designed to measure accurately currents as small as
2% of the nominal current). The rating factor of a CT is largely
dependent upon ambient temperature. Most CTs have rating factors for 35
degrees Celsius and 55 degrees Celsius. A CT usually demonstrates
reduced capacity to maintain accuracy with rising ambient temperature.
It is important to be mindful of ambient temperatures and resultant
rating factors when CTs are installed inside pad-mounted transformers or
poorly ventilated mechanical rooms. Recently, manufacturers have been
moving towards lower nominal primary currents with greater rating
factors. This is made possible by the development of more efficient
ferrites and their corresponding hysteresis curves. This is a distinct
advantage over previous CTs because it increases their range of
accuracy. For example, a 200:5 CT with a rating factor of 4.0 is most
accurate between 20A (light load) and 800A (4.0 times the nominal
rating, or "full load," of the CT) of primary current. While previous
revisions of CTs were on the order of 500:5 with a rating factor of 1.5
yielding an effective range of 50A to 750A. This is an 11% increase in
effective range for two CTs that would be used at similar services. Not
to mention, the relative cost of a 500:5 CT is significantly greater
than that of a 200:5.
Physical CT configuration is another important factor in reliable CT
accuracy. While all electrical engineers are quite comfortable with
Gauss' Law, there are some issues when attempting to apply theory to the
real world. When conductors passing through a CT are not centered in the
circular (or oval) void, slight inaccuracies may occur. It is important
to center primary conductors as they pass through CTs to promote the
greatest level of CT accuracy. After all, in an electric metering
circuit, the most inaccurate component is the CT.
Current transformers (CTs) are commonly used in metering and protective
relaying in the electrical power industry where they facilitate the safe
measurement of large currents, often in the presence of high voltages.
The current transformer safely isolates measurement and control
circuitry from the high voltages typically present on the circuit being
measured.
Current transformers are often constructed by passing a single primary
turn (either an insulated cable or an uninsulated bus bar) through a
well-insulated toroidal core wrapped with many turns of wire. Current
transformers are used extensively for measuring current and monitoring
the operation of the power grid. The CT is typically described by its
current ratio from primary to secondary. Common secondaries are 1 or 5
amperes. For example, a 4000:5 CT would provide an output current of 5
amperes when the primary was passing 4000 amperes. The secondary winding
can be single ratio or multi ratio, with five taps being common for
multi ratio CTs. Typically, the secondary connection points are labeled
as 1s1, 1s2, 2s1, 2s2 and so on. The multi ratio CTs are typically used
for current matching in current differential protective relaying
applications. Often, multiple CTs will be installed as a "stack" for
various uses (for example, protection devices and revenue metering may
use separate CTs). For a three-stacked CT application, the secondary
winding connection points are typically labeled Xn, Yn, Zn. Care must be
taken that the secondary of a current transformer is not disconnected
from its load while current is flowing in the primary, as this will
produce a dangerously high voltage across the open secondary and may
permanently affect the accuracy of the transformer.
Specially constructed wideband current transformers are also used
(usually with an oscilloscope) to measure waveforms of high frequency or
pulsed currents within pulsed power systems. One type of specially
constructed wideband transformer provides a voltage output that is
proportional to the measured current. Another type (called a Rogowski
coil) requires an external integrator in order to provide a voltage
output that is proportional to the measured current. Unlike CTs used for
power circuitry, wideband CTs are rated in output volts per ampere of
primary current.
Pulse Transformers
A pulse transformer is a transformer that is optimized for
transmitting rectangular electrical pulses (that is, pulses with fast
rise and fall times and a constant amplitude). Small versions called
signal types are used in digital logic and telecommunications circuits,
often for matching logic drivers to transmission lines. Medium-sized
power versions are used in power-control circuits such as camera flash
controllers. Larger power versions are used in the electrical power
distribution industry to interface low-voltage control circuitry to the
high-voltage gates of power semiconductors. Special high voltage pulse
transformers are also used to generate high power pulses for radar,
particle accelerators, or other high energy pulsed power applications.
To minimize distortion of the pulse shape, a pulse transformer needs to
have low values of leakage inductance and distributed capacitance, and a
high open-circuit inductance. In power-type pulse transformers, a low
coupling capacitance (between the primary and secondary) is important to
protect the circuitry on the primary side from high-powered transients
created by the load. For the same reason, high insulation resistance and
high breakdown voltage are required. A good transient response is
necessary to maintain the rectangular pulse shape at the secondary,
because a pulse with slow edges would create switching losses in the
power semiconductors.
The product of the peak pulse voltage and the duration of the pulse (or
more accurately, the voltage-time integral) is often used to
characterize pulse transformers. Generally speaking, the larger this
product, the larger and more expensive the transformer.
Speaker Transformers
In the same way that transformers are used to create high voltage power
transmission circuits that minimize transmission losses, speaker
transformers allow many individual loudspeakers to be powered from a
single audio circuit operated at higher-than normal speaker voltages.
This application is common in public address (e.g., Tannoy)
applications. Such circuits are commonly referred to as constant voltage
or 70 volt speaker circuits although the audio waveform is obviously a
constantly changing voltage.
At the audio amplifier, a large audio transformer may be used to step-up
the low impedance, low-voltage output of the amplifier to the designed
line voltage of the speaker circuit. Then, a smaller transformer at each
speaker returns the voltage and impedance to ordinary speaker levels.
The speaker transformers commonly have multiple primary taps, allowing
the volume at each speaker to be adjusted in a number of discrete steps.
Use of a constant-voltage speaker circuit means that there is no need to
worry about the impedance presented to the amplifier output (which would
clearly be too low if all of the speakers were arranged in parallel and
would be too complex a design problem if the speakers were arranged in
series-parallel). The use of higher transmission voltage and impedance
means that power lost in the connecting wire is minimized, even with the
use of small-gauge conductors (and leads to the term constant voltage as
the line voltage doesn't change much as additional speakers are added to
the system). In addition, the ability to adjust, locally, the volume of
each speaker (without the complexity and power loss of an L pad) is a
useful feature.
Power Transformer Information:
|
 
Power Transformer Types
 |
Step Up and Step Down Transformers
to Power transformers to step-up ( raise) or step-down (lower) the
electrical voltage.
|
 |
Isolation Transformers
allows signal or power to be taken from one device and fed into
another without electrically connecting the two.
|
 |
Toroidal Transformers
are devices that transfer electrical energy from one electric
circuit to another, without changing the frequency, by
electromagnetic induction.
|

|
Custom
Transformers
are designed to meet certain performance specifications and size
requirement that you require. There is a wide range of custom
transformer types.
|

|
Buck Boost Transformers
is a ideal solution for changing line voltage by small amounts.
Often used to buck (lower), or boost (raise) the voltage from 208v
to 240v for lighting applications.
|

|
Pole Mounted Transformers
are mounted to poles for overhead electrical lines. Used in various applications.
Are available in single phase or three phase transformers.
|

|
Medium Voltage Transformers
are used with a medium range of voltages. They come in a full
range from liquid-filled, convention dry type as well as cast coil.
|
 |
Pad Mounted Transformers
are a excellent choice for commercial and industrial such as
manufacturing facilities, refineries, office buildings, schools,
hospitals, restaurants, and retail stores. They come in various
sizes and can be used underground as well.
|
 |
High
Voltage Transformers
typically these voltage transformers are used in power transmission
applications. High voltage transformers are also used in microwave.
|
|
- ACME Transformers
- With Acme Electric being in business
over 80 years, they have always believed in offering there customers superior service, quality and technical expertise in the
transformer market.
-
AMVECO Transformers -
AMVECO designs and manufactures toroids
transformers, current transformers, and auto transformers. Most
AMVECO products are custom designed utilizing their state-of-art proprietary
CAD programs. The AMVECO engineers can quickly generate designs in a
matter of hours, if needed.
-
Federal Pacific Transformers -
Federal Pacific is a division of Electro- Mechanical Corporation, a
privately held, American owned company founded in 1958. Federal
pacific offers dry-type transformers from .050 KVA through 10,000
KVA single and three phase, up to 34.5 KV, 150 KV BIL with UL
approval through 15 KV.
-
Marcus Transformer - Ever since they opened their doors for business a half a century ago,
they have been a leader in innovative transformer design. As a
family-owned company they are proud of the reputation they have
earned for making quality-built transformers that deliver
exceptional performance and savings.
-
Hammond Transformers - Hammond Manufacturing was founded in 1917 in Guelph, Ontario,
Canada. In the last 3 decades it has expanded to the US and the
international markets offering many types of power transformers.
- TEMCo Transformers
- TEMCo a family-owned business has been
manufacturing and distributing electrical products since
1968. They focus on transformers that significantly
reduce power consumption over 30 percent compared to competitive
makes.
- GE Transformers - GE has been a key player in the energy industry for
more than a century. Since the installation of
their first steam turbine in 1901. They have become
number one provider of high-technology power generation
equipment.
-
Jefferson Electric Transformers - Jefferson Electric has
been a pioneer and innovator of magnetic products since 1915.
Jefferson broad line of dry-type transformers are backed by quality
assurance systems so stringent that each and every unit gets
thoroughly tested before it goes out there door.
-
More power transformer brands -
Check out more companies by clinking this link.
Power Transformer Types
-
Distribution Transformers - Distribution Transformers are generally used in electrical power
distribution and transmission power. This class of transformer has
the highest power, or volt-ampere ratings. and the highest
continuous voltage rating.
-
Substation Transformers -
Substation transformers are large
devices which usually weigh tens of thousands of pounds. They are
filled with tens of thousands of gallons of heat transfer fluid.
Although they are typically 99.8% efficient in the transforming of
electricity from one voltage to another, processing hundreds of Mega
Volts-Amps of electricity force the liberation of hundreds of BTUs
per second.
-
Medical Grade Isolation
Transformer -
Medical Grade Transformers generally refer to the transformers
used in medical devices as well as hospital, biomedical and patient
care equipment. There are a number of strict safety rules,
guidelines and laws governing the design, construction and the test
of these transformers.
-
Drive Isolation Transformer -
They are used to adjust the speed of induction motors by varying
the frequency. They are becoming more popular because of their
impact on energy saving, and they are easy to control.
-
Toroidal Transformers -
Toroidal transformers are more efficient than the cheaper laminated
EI types of similar power level. Some of the advantages are smaller
size, lower weight, less mechanical hum, (making them superior in
audio amplifier), low-off-load loss.
|
-
Step-Up Transformers - A Step-Up Transformer is one whose
secondary voltage is greater than its primary voltage.
This kind of transformer "steps up" the voltage applied
to it. -
-
Step-Down Transformers
- A Step-Down Transformer is designed to reduce voltage from primary to
secondary.
They can range from sizes from .05 kva to 500 kva
-
Isolation Transformers -
An isolation transformer is a device that transfers energy from
the alternating current (AC) supply to an electrical or electronic
load. It isolates the windings to prevent transmitting certain
types of harmonics.
-
Buck Boost Transformers - Buck Boost
Transformers make small adjustments to the incoming voltage. They
are often used to change voltage from 208v to 240v for lighting
applications. One major advantages of Buck boost transformers
are their low cost, compact size and light weight.
-
High Voltage Transformer - There are many different types of
voltage transformers. A high voltage transformer operates with high
voltages. Typically, these voltage transformers are used in power
transmission applications, where voltages are high enough to present
a safety hazard.
-
Medium Voltage Transformers -
A medium voltage transformer can be connected directly to a primary
distribution circuit and generally has the most load diversity.
These voltage transformers have installation practices that are
generally in accordance with application recommendations from the
Institute of Electrical and Electronic Engineers (IEEE).
-
Low Voltage Transformers
- A low voltage transformer is an electrical device that transforms
120 volts (line voltage) into 12 volts or 24 volts (low voltage).
Some uses for low voltage transformer are in landscaping lighting.
-
Single Phase Transformers - In electrical engineering, single-phase electric power refers to the
distribution of electric power using a system in which all the
voltages of the supply vary in unison. Single-phase distribution is
used when loads are mostly lighting and heating, with few large
electric motors.
-
Three Phase Transformers - Three Phase Transformers must have 3 coils or windings connected in
the proper sequence in order to match the incoming power and
therefore transform the power company voltage to the level of
voltage needed while maintaining the proper phasing or polarity.
-
Custom Transformers -
Custom transformers are designed for a certain performance
specifications and size requirements. The company works with
your engineering specification.
-
Industrial Control Transformers -
Industrial Control Transformers are used to convert the
available supply voltage to the required voltage to supply
industrial control circuits and motor control loads.
-
Pad Mounted Transformers - Pad Mounted Transformers are usually single phase or three phase and
is used where safety is a main concern. Typical Application is
restaurant, commercial building, shopping mall, institutional.
-
Pole Mounted Transformers -
Pole Mounted Transformers are used for distribution in areas
with overhead primary lines. Outside a typical house one can see one
of these devices mounted on the top of an electrical pole.
-
Oil Filled Transformers - Oil-filled transformers are transformers that use insulating oil as
insulating materials. The oil helps cool the transformer.
Because it also provides part of the electrical insulation between
internal live parts, transformer oil must remain stable at high
temperatures over an extended period.
-
Dry Type Transformers - Dry-type transformers are available for voltages up through 34.5 kV
(although the most common upper limit is 15) and kVA ratings up
through 10,000 (with 5000 as the usual limit). Dry-type use air as a
coolant, lowering health and environmentally concerns.
- Auto Transformers -
An autotransformer is an electrical transformer with only one
winding. The winding has at least three electrical connection points
called taps. Autotransformers are frequently used in power
applications to interconnect systems operating at different voltage
classes, for example 138 kV to 66 kV for transmission. Another
application is in industry to adapt machinery built for 480 V
supplies to operate on the local 600 V supply.
- More power transformer types - Read further about additional
transformer types and their uses.
|
-
Electrical
Transformers -
electrical transformers are devices used to raise or lower the
voltage of alternating current. For instance, power is transported
over long distance in high voltage power lines and then transformers
lower the voltage so that the power can be used by household.
-
Isolating
Transformers -
Isolating transformer is a transformer, often with
symmetrical windings, which is used to decouple two circuits.
An Isolation transformer allows an AC signal or power to be taken
from one device and fed into another without electrically connecting
the two circuits. Isolation transformers block transmission of DC
signals from one circuit to the other, but allow AC signals to pass.
-
Transmission
Power Lines - A transmission line is the material medium or structure that forms
all or part of a path from one place to another for directing the
transmission of energy, such as electromagnetic
or acoustic waves as well as electric power
transmission. Components of transmission lines include wires, coaxial
cables, dielectric slabs, option fibers,
electric power lines, and waveguides.
-
Transformer Voltage - The measure of the amount of force on a
unit charge because of the surrounding charge.
-
Transformer Phase - Most transformer are either single phase
or three phase.
-
Transformer Frequency -
The transformer cannot change the frequency of the supply. If the
supply is 60 hertz, the output will also be 60 hertz.
-
Transformer K Factor - Some transformers are now being offered
with a k-factor rating. This measure the transformer's ability to
withstand the heating effects of non-sinusoidal harmonic currents
produced by much of today's electronic equipment and certain
electrical equipment.
-
Primary Voltage -The coil winding that is directly connected
to the input power.
-
Secondary Voltage -The coil winding supplying the output
voltage.
-
Harmonic Cancellation -
Harmonic cancellation is performed with harmonic canceling
transformers also known as phase-shifting transformers. A harmonic
canceling transformer is a relatively new power quality product for
mitigating harmonic problems in electrical distribution systems.
This type of transformer has patented built-in electromagnetic
technology designed to remove high neutral current and the most
harmful harmonics from the 3rd through 21st.
- Weatherproof -
Enclosed transformers come with a weatherproof standard set by
NEMA.
- Epoxy Encapsulated -
A process in which a transformer or one of its components is
completely sealed with epoxy or a similar material. This process is
normally preferred when a unit might encounter harsh environmental
conditions.
-
More power transformer terms -Such as inductor, ground fault,
core saturation, current transformer, faraday shield.
Related Transformer Products
-
Voltage Regulators - A voltage regulator is an electrical regulator designed to
automatically maintain a constant voltage level.
It may use an electromechanical mechanism, or passive or active
electronic components. Depending on the design, it may be used to
regulate one or more AC or DC voltages.
-
AC Line Reactor -
AC Line Reactors is a three phase transformer used in
conjunction with AC variable frequency and DC motor drive.
They are a bi-directional protective filtering device.
-
Line Power Conditioners -
Power or line conditioners regulate, filter, and suppress noise in
AC power for sensitive computer and other solid state equipment.
-
DC Power Supplies -
Conversion of one form of electrical power to another desired
form and voltage. This typically involves converting 120 or 240 volt
AC supplied by a utility company to a well-regulated
lower voltage DC for electronic devices.
-
Rotary Phase Converters -
Rotary phase converters are most commonly used in home or small
commercial or industrial settings. Rotary phase converters convert
single-phase power into three-phase power. This is a very
cost-effective way to power three-phase electric motors
-
Frequency Converters -
A frequency changer or frequency converter is an
electronic device that converts alternating current (AC) of one
frequency to alternating current of another frequency.
-
Voltage Converters -
A voltage converter changes the voltage of an electrical power
source and is usually combined with other components to create a
power supply.
-
Magnetic Motor Starters - Magnetic Motor starters are
essentially heavy duty relays mounted in boxes, often equipped with
heater/thermal overloads matched to the motor they start.
-
Motor Starting Auto Transformers - An Auto transformer starter uses an auto transformer to reduce
the voltage applied to a motor during start. The auto transformer
may have a number of output taps and be set-up to provide a single
stage starter, or a multistage starter.
For an additional resource the
Best of Industry Web Directory
:
Electrical Power Transformer Directory section is quite useful. |