Transmission Power Lines
Most
transmission lines operate with three-phase alternating current (ac).
The standard frequency in North America is 60 Hz; in Europe, 50 Hz. The
three-phase system has three sets of phase conductors. Long-distance
energy transmission occasionally uses high-voltage direct-current (dc)
lines. An electric power transmission system interconnects
generators and loads and generally provides multiple paths among them.
Multiple paths increase system reliability because the failure of one
line does not cause a system failure.
To Order Power Transformers We Recommend TEMCo
Ph:
1-800-613-2290
Or 1-510-490-2187
Link:
Power Transformer |
The electric power system can be divided into the distribution,
subtransmission, and transmission systems. With operating voltages less
than 34.5 kV, the distribution system carries energy from the local
substation to individual households, using both overhead and underground
lines. With operating voltages of 69-138 kV, the subtransmission system
distributes energy within an entire district and regularly uses overhead
lines. With operating voltage exceeding 230 kV, the transmission system
interconnects generating stations and large substations located close to
load centers by using overhead lines.
Transmission lines take many forms and have
application in many areas. For example, they traverse the countryside,
carrying telephone signals and electric power. The same transmission
lines, with similar functions, may be hidden above false ceilings in
urban buildings. Optical fibers are installed in
data-intensive buildings and form a nationwide network. Increasing
demand also requires that transmission lines handle greater values of
electric power.
Electric power generating stations and load consumption
centers are connected by a network of power transmission lines, mostly
overhead lines. Power transmitted is generally in the form of
three-phase alternating current (ac) at 60 or 50 Hz. In a few instances,
where a clear technical or economic advantage exists, direct-current
(dc) systems may be used. As the distances over which the power must be
transmitted become great and as the amount of power transmitted
increases, the power lost in the transmission lines becomes an important
component of the production cost of electricity, and it becomes
advantageous to increase the transmission voltage. This basic
consideration has led to electric power networks which use higher
voltages for long-distance bulk power transfers, with several layers of
underlying regional networks at progressively lower voltages which
extend over shorter distances. The most common transmission voltages in
use are 765, 500, 400, 220 kV, and so forth. Voltages below 69 kV are
termed subtransmission or distribution voltages, and at these and lower
voltages the networks may have fewer alternative supply paths (loops) or
may be entirely radial in structure.
Overhead alternating-current transmission
Overhead transmission lines distribute the majority of
the electric energy in the system. A typical high-voltage line has three
phase conductors to carry the current and transport the energy, and two
grounded shield conductors to protect the line from direct lightning
strikes. The usually bare conductors are insulated from the supporting
towers by insulators attached to grounded towers or poles. Lower-voltage
lines use post insulators, while the high-voltage lines are built with
insulator chains or long-rod composite insulators. The normal distance
between the supporting towers is a few hundred feet.
Transmission lines use ACSR (aluminum cable, steel reinforced) and ACAR
(aluminum cable, alloy reinforced) conductors. In an ACSR conductor, a
stranded steel core carries the mechanical load, and layers of stranded
aluminum surrounding the core carry the current. An ACAR conductor is a
stranded cable made of an aluminum alloy with low resistance and high
mechanical strength. ACSR conductors are usually used for high-voltage
lines, and ACAR conductors for subtransmission and distribution lines.
Ultrahigh-voltage (UHV) and extrahigh-voltage (EHV) lines use bundle
conductors. Each phase of the line is built with two, three, or four
conductors connected in parallel and separated by about 1.5 ft (0.5 m).
Bundle conductors reduce corona discharge. .
Transmission lines are subject to environmental adversities, including
wide variations of temperature, high winds, and ice and snow deposits.
Typically designed to withstand environmental stresses occurring once
every 50–100 years, lines are intended to operate safely in adverse
conditions.
Variable weather affects line operation. Extreme weather reduces corona
inception voltage, leading to an increase in audible noise, radio noise,
and telephone interference. Load variation requires regulation of line
voltage. A short circuit generates large currents, overheating
conductors and producing permanent damage.
The power that a line can transport is limited by the line's electrical
parameters. Voltage drop is the most important factor for distribution
lines; where the line is supplied from only one end, the permitted
voltage drop is about 5%.
Conductor temperature must be lower than the temperature which causes
permanent elongation. A typical maximum steady-state value for ACSR is
212°F (100°C), but in an emergency temperatures 10–20% higher are
allowed for a short period of time (10 min to 1 hour).
Corona discharge is generated when the electric field at the surface of
the conductor becomes larger than the breakdown strength of the air. The
oscillatory nature of the discharge generates high-frequency,
short-duration current pulses, the source of corona-generated radio and
television interference. Surface irregularities such as water droplets
cause local field concentration, enhancing corona generation. Thus,
during bad weather, corona discharge is more intense and losses are much
greater. Corona discharge also generates audible noise with two
components: a broad-band, high-frequency component, which produces
crackling and hissing, and a 120-Hz pure tone.
Underground power transmission
Most cities use underground cables to distribute
electrical energy. These cables virtually eliminate negative
environmental effects and reduce electrocution hazards. However, they
entail significantly higher construction costs.
Underground cables are divided into two categories: distribution cables
(less than 69 kV) and high-voltage power-transmission cables (69–500
kV).
Extruded solid dielectric cables dominate in the 15–33-kV urban
distribution system. In a typical arrangement, the stranded copper or
aluminum conductor is shielded by a semiconductor layer, which reduces
the electric stress on the conductor's surface. Oil-impregnated
paper-insulated distribution cables are used for higher voltages and in
older installations.
Cable temperatures vary with load changes, and cyclic thermal expansion
and contraction may produce voids in the cable. High voltage initiates
corona in the voids, gradually destroying cable insulation. Low-pressure
oil-filled cable construction reduces void formation. A single-phase
concentric cable has a hollow conductor with a central oil channel.
Three-phase cables have three oil channels located in the filler.
Types of electrical transmission line
Coaxial cable
Coaxial lines confine the electromagnetic wave to the area inside the
cable, between the center conductor and the shield. The transmission of
energy in the line occurs totally through the dielectric inside the
cable between the conductors. Coaxial lines can therefore be bent and
twisted (subject to limits) without negative effects, and they can be
strapped to conductive supports without inducing unwanted currents in
them.
In radio-frequency applications up to a few gigahertz, the wave
propagates in the transverse electric and magnetic mode (TEM), which
means that the electric and magnetic fields are both perpendicular to
the direction of propagation. However, above a certain frequency called
the cutoff frequency, the cable behaves as a waveguide, and propagation
switches to either a transverse electric (TE) or a transverse magnetic
(TM) mode or a mixture of modes. This effect enables coaxial cables to
be used at microwave frequencies, although they are not as efficient as
the more expensive, purpose-built waveguides.
The most common use for coaxial cables is for television and other
signals with bandwidth of multiple Megahertz. In the middle 20th Century
they carried long distance telephone connections.
Microstrip
A microstrip circuit uses a thin flat conductor which is parallel to a
ground plane. Microstrip can be made by having a strip of copper on one
side of a printed circuit board (PCB) or ceramic substrate while the
other side is a continuous ground plane. The width of the strip, the
thickness of the insulating layer (PCB or ceramic) and the dielectric
constant of the insulating layer determine the characteristic impedance.
Stripline
A stripline circuit uses a flat strip of metal which is sandwiched
between two parallel ground planes, The insulating material of the
substrate forms a dielectric. The width of the strip, the thickness of
the substrate and the relative permittivity of the substrate determine
the characteristic impedance of the strip which is a transmission line.
Lecher lines
Lecher lines are a form of parallel conductor that can be used at UHF
for creating resonant circuits. They are used at frequencies between HF/VHF
where lumped components are used, and UHF/SHF where resonant cavities
are more practical.
Pulse generation
Transmission lines are also used as pulse generators. By
charging the transmission line and then discharging it into a resistive
load, a rectangular pulse equal in length to twice the electrical length
of the line can be obtained, although with half the voltage. A Blumlein
transmission line is a related pulse forming device that overcomes this
limitation. These are sometimes used as the pulsed energy sources for
radar transmitters and other devices.
Stub filters
If a short-circuited or open-circuited transmission line
is wired in parallel with a line used to transfer signals from point A
to point B, then it will function as a filter. The method for making
stubs is similar to the method for using Lecher lines for crude
frequency measurement, but it is working backwards. One method
recommended in the RSGB's radio communication handbook is to take an
open-circuited length of transmission line wired in parallel with the
feeder delivering signals from an aerial. By cutting the free end of the
transmission line, a minimum in the strength of the signal observed at a
receiver can be found. At this stage the stub filter will reject this
frequency and the odd harmonics, but if the free end of the stub is
shorted then the stub will become a filter rejecting the even harmonics.
Power Transformer Information:
|